Scope. One primary weather station per city, with NOAA/ASHRAE 99% heating and 1% cooling values from NOAA NCEI Engineering Weather Data (mostly 1988–2017 records). Example loads are for one illustrative house and are not a design. Your building department may require specific design values. Not ACCA approved or certified.

Design temperatures and example loads

Example columns are for the same house in every city: 2,000 sq ft, one story, 8-foot ceilings, good insulation, 200 sq ft of low-E windows, ducts where they usually are locally. Loads are in Btuh. Sorted by climate zone.

CityZone99% heating1% coolingGrainsHeating loadCooling loadNominal size
Miami, FL1A53°F91°F5714,98128,4612.5 tons
Austin, TX2A30°F99°F2529,69229,7072.5 tons
Dallas, TX2A27°F99°F2531,78029,8192.5 tons
Houston, TX2A34°F95°F4527,21429,6282.5 tons
New Orleans, LA2A36°F93°F5525,94929,7892.5 tons
Orlando, FL2A43°F92°F4621,44627,9602.5 tons
San Antonio, TX2A33°F97°F2527,72828,5972.5 tons
Tampa, FL2A43°F91°F5321,45628,3842.5 tons
Phoenix, AZ2B42°F108°F-1721,94829,1942.5 tons
Atlanta, GA3A27°F91°F3431,69326,3392.5 tons
Charlotte, NC3A25°F92°F3431,59925,9652.5 tons
Nashville, TN3A19°F92°F3735,32126,2782.5 tons
Las Vegas, NV3B34°F107°F-2826,86628,5952.5 tons
Los Angeles, CA3B46°F81°F-219,62518,5102 tons
Sacramento, CA3B34°F97°F-727,38624,6002.5 tons
San Diego, CA3B46°F81°F519,63919,2002 tons
Kansas City, MO4A7°F93°F4740,87426,3992.5 tons
New York, NY4A18°F90°F2934,64323,8012 tons
Philadelphia, PA4A18°F91°F3434,64024,3832.5 tons
Washington, DC4A21°F92°F3832,86325,2912.5 tons
Portland, OR4C29°F88°F-129,45021,3322 tons
Seattle, WA4C30°F82°F-528,75017,6941.5 tons
Boston, MA5A13°F88°F2639,03122,5172 tons
Chicago, IL5A3°F89°F3345,00323,2632 tons
Detroit, MI5A9°F88°F2841,32422,3062 tons
Denver, CO5B6°F91°F-4040,20919,2202 tons
Salt Lake City, UT5B14°F96°F-3335,97421,7222 tons
Minneapolis, MN6A−6°F88°F2951,67622,4452 tons

Across the list, Minneapolis, MN has the coldest heating design temperature at −6°F, Phoenix, AZ the hottest cooling design temperature at 108°F, and Miami, FL the most design grains at 57. The same house needs very different equipment in each, which is why a square-foot rule cannot size it.

What the columns mean

  • 99% heating is the outdoor temperature the location stays above for 99% of the year’s hours. Manual J sizes heating to it, not to the record low.
  • 1% cooling is the temperature exceeded for only 1% of hours. Cooling is sized to it, not to the hottest day on record.
  • Grains is the outdoor moisture above an indoor target of 75°F and 50% relative humidity. High grains mean a big latent load; negative grains mean the outdoor air is drier than indoors at the design condition.
  • Zone is the 2021 IECC climate zone for the county, which sets insulation and equipment rules in codes that adopt that edition.

Using them in a load calculation

Use the design values as published, without adding safety factors to them. Pick the station closest to the house in climate rather than just in distance: coastal and inland stations in the same metro can differ by several degrees, which is a ton or more in Los Angeles or San Diego. Where the building department publishes its own design values, use theirs.

The free Manual J calculator and the app pick a station from the ZIP code. For Canadian locations, see Canadian design temperatures by city.

FAQ

What are the 99% and 1% design temperatures?

The 99% heating design temperature is the outdoor temperature a location stays above for 99% of the hours in a typical year. The 1% cooling design temperature is the one it exceeds for only 1% of hours. Manual J sizes equipment to these values, not to record highs or lows, so the system is right-sized for almost every hour it runs.

Where do Manual J design temperatures come from?

Manual J calls for the 99% heating and 1% cooling outdoor design conditions for the location. The values on this site come from NOAA NCEI’s Engineering Weather Data, which reports those ASHRAE-defined values for each weather station from hourly observations, mostly 1988–2017. Where your building department publishes its own design values, use theirs.

Why do other sources give a slightly different number?

Design values depend on the weather station and the years of data behind them. ZIP-based tools map each ZIP to a reference station, and published tables use different periods of record, so differences of a few degrees are common. Use the station closest to the house in climate, and any values your building department requires.

Are these the same as Canadian design temperatures?

No. Canada uses the 2.5% January and July values from the National Building Code for CSA F280 work. See the Canadian design temperatures guide for those.