Scope. Outdoor design conditions and illustrative block loads for homes in and around Detroit, MI. The example loads are estimates for typical houses, not a design for yours. Your building department may require specific design values. Not ACCA approved or certified, and not a stamped design.

Detroit design conditions

Weather stationColeman A. Young International Airport (Detroit City) (KDET)
SourceNOAA NCEI Engineering Weather Data, 1988–2017 observations
Elevation626 ft
99% heating design temperature (NOAA/ASHRAE)9°F
1% cooling design temperature (NOAA/ASHRAE)88°F
Mean coincident wet bulb72°F
Design grains (75°F, 50% RH indoors)28
Daily rangeMedium (July average 17°F)
IECC climate zone5A (Wayne County, 2021 IECC)
Nearby stationSelfridge ANGB (north suburbs) (KMTC): 7°F heating, 87°F cooling

With Manual J’s default indoor conditions of 70°F in winter and 75°F in summer, the heating load is driven by a 61°F difference and the cooling load by a 13°F difference, before sun, people and moisture are added. 28 design grains means a real latent load on top of the sensible load, so the equipment has to dehumidify as well as cool.

What drives loads in Detroit

NOAA lists Coleman A. Young (Detroit City) Airport at 88°F cooling and 9°F heating, with 28 design grains. Selfridge, out in the north suburbs, is 87°F and 7°F.

Brick colonials, bungalows and ranches with full basements make up much of the housing. The furnace, ducts and often a finished rec room are down there, and how that space is entered changes the heat loss a lot.

Typical loads for Detroit homes

Four illustrative houses, each with 8-foot ceilings and ducts in the basement unless noted, at the design conditions above:

HouseHeating loadCooling loadNominal sizeSq ft per ton
Older 1,500 sq ft one-story
fair insulation, double-pane windows
48,626 Btuh24,572 Btuh2.5 tons733
2,000 sq ft one-story, built to code
good insulation, low-E windows
41,324 Btuh22,306 Btuh2 tons1,076
2,600 sq ft two-story, built to code
good insulation, low-E windows
45,846 Btuh25,572 Btuh2.5 tons1,220
2,000 sq ft high-performance
excellent insulation and air sealing, ducts inside
32,060 Btuh19,894 Btuh2 tons1,206

The spread is the point. The older 1,500 sq ft house needs 48,626 Btuh of heat, more than the 2,000 sq ft high-performance house at 32,060 Btuh, despite being 500 sq ft smaller. No square-foot rule can see that. These are whole-house block loads from the same engine the free Manual J calculator and the app use; a room-by-room load for a real house will differ.

Common sizing mistakes in Detroit

  • Replacing an old 100,000 BTU furnace with the same size high-efficiency model.
  • Leaving out the basement walls and rim joists, a big source of heat loss in older homes.
  • Oversizing the AC. At 88°F, a code-built house rarely needs as much tonnage as people expect.

Heat pumps in Detroit

Cold-climate heat pumps can carry much of the Detroit winter; at 9°F, check capacity at 5°F. Dual-fuel with a gas furnace is a common setup. The cold-climate heat pump guide walks through capacity at the design temperature, the balance point and backup heat.

Run a load for your Detroit house

The free Manual J calculator takes a ZIP code and eight inputs and returns a whole-house heating and cooling load in the browser. The HVAC Load Calculator app goes further at the house: room-by-room loads, Manual S equipment sizes and a PDF report.

FAQ

What is the design temperature for Detroit's suburbs?

City Airport's 9°F heating and 88°F cooling suit the city and inner suburbs; Selfridge, at 7°F, fits the colder north side better. Pick the station nearest the house in climate; a ZIP-based lookup in a Manual J tool does this for you.

What is the Manual J design temperature for Detroit, MI?

NOAA’s Engineering Weather Data lists Coleman A. Young International Airport (Detroit City) at 9°F for the 99% heating design and 88°F for the 1% cooling design, with a 72°F mean coincident wet bulb, from 1988–2017 observations. Use the station closest to the house in climate, and any value your building department requires.

What size AC do I need for a 2,000 sq ft house in Detroit?

It depends on the house, not the floor area. In our example, a code-built 2,000 sq ft one-story with low-E windows and ducts in the basement comes out at about 22,306 Btuh of cooling, a 2-ton nominal size, or about 1,076 sq ft per ton. An older or leakier house needs more; run a load for the actual house.