Scope. Outdoor design conditions and illustrative block loads for homes in and around Philadelphia, PA. The example loads are estimates for typical houses, not a design for yours. Your building department may require specific design values. Not ACCA approved or certified, and not a stamped design.

Philadelphia design conditions

Weather stationPhiladelphia International Airport (KPHL)
SourceNOAA NCEI Engineering Weather Data, 1988–2017 observations
Elevation36 ft
99% heating design temperature (NOAA/ASHRAE)18°F
1% cooling design temperature (NOAA/ASHRAE)91°F
Mean coincident wet bulb74°F
Design grains (75°F, 50% RH indoors)34
Daily rangeMedium (July average 16°F)
IECC climate zone4A (Philadelphia County, 2021 IECC)
Nearby stationNortheast Philadelphia Airport (KPNE): 17°F heating, 91°F cooling

With Manual J’s default indoor conditions of 70°F in winter and 75°F in summer, the heating load is driven by a 52°F difference and the cooling load by a 16°F difference, before sun, people and moisture are added. 34 design grains means a real latent load on top of the sensible load, so the equipment has to dehumidify as well as cool.

What drives loads in Philadelphia

NOAA lists Philadelphia International at 91°F cooling and 18°F heating, with 34 design grains. Northeast Philadelphia is 91°F and 17°F.

Much of the housing is older masonry with little insulation and heat that was originally from radiators. Adding central air or a heat pump means fitting ducts or going ductless, and the house's leakage often dominates the winter load.

Typical loads for Philadelphia homes

Four illustrative houses, each with 8-foot ceilings and ducts in the basement unless noted, at the design conditions above:

HouseHeating loadCooling loadNominal sizeSq ft per ton
Older 1,500 sq ft one-story
fair insulation, double-pane windows
40,953 Btuh27,085 Btuh2.5 tons665
2,000 sq ft one-story, built to code
good insulation, low-E windows
34,640 Btuh24,383 Btuh2.5 tons984
2,600 sq ft two-story, built to code
good insulation, low-E windows
38,672 Btuh28,078 Btuh2.5 tons1,111
2,000 sq ft high-performance
excellent insulation and air sealing, ducts inside
26,813 Btuh21,471 Btuh2 tons1,118

The spread is the point. The older 1,500 sq ft house needs 40,953 Btuh of heat, more than the 2,000 sq ft high-performance house at 26,813 Btuh, despite being 500 sq ft smaller. No square-foot rule can see that. These are whole-house block loads from the same engine the free Manual J calculator and the app use; a room-by-room load for a real house will differ.

Common sizing mistakes in Philadelphia

  • Sizing a new ducted system to the old boiler's output. Boilers were often heavily oversized.
  • Treating a rowhome like a detached house. Party walls cut the load substantially.
  • Leaving out the third-floor and roof loads, where most of the summer heat comes in.

Heat pumps in Philadelphia

Heat pumps, including ductless ones, are a common upgrade path for Philadelphia rowhomes. At 18°F, check the unit's capacity at that temperature and keep backup heat for the gap. The cold-climate heat pump guide walks through capacity at the design temperature, the balance point and backup heat.

Run a load for your Philadelphia house

The free Manual J calculator takes a ZIP code and eight inputs and returns a whole-house heating and cooling load in the browser. The HVAC Load Calculator app goes further at the house: room-by-room loads, Manual S equipment sizes and a PDF report.

FAQ

Can I size a heat pump from my old boiler in Philadelphia?

No. Old boilers were often far bigger than the heat loss, and many houses have since had windows or insulation upgraded. Run a Manual J heat loss at the 18°F design temperature instead.

What is the Manual J design temperature for Philadelphia, PA?

NOAA’s Engineering Weather Data lists Philadelphia International Airport at 18°F for the 99% heating design and 91°F for the 1% cooling design, with a 74°F mean coincident wet bulb, from 1988–2017 observations. Use the station closest to the house in climate, and any value your building department requires.

What size AC do I need for a 2,000 sq ft house in Philadelphia?

It depends on the house, not the floor area. In our example, a code-built 2,000 sq ft one-story with low-E windows and ducts in the basement comes out at about 24,383 Btuh of cooling, a 2.5-ton nominal size, or about 984 sq ft per ton. An older or leakier house needs more; run a load for the actual house.