Scope. Outdoor design conditions and illustrative block loads for homes in and around Philadelphia, PA. The example loads are estimates for typical houses, not a design for yours. Your building department may require specific design values. Not ACCA approved or certified, and not a stamped design.
Philadelphia design conditions
| Weather station | Philadelphia International Airport (KPHL) |
|---|---|
| Source | NOAA NCEI Engineering Weather Data, 1988–2017 observations |
| Elevation | 36 ft |
| 99% heating design temperature (NOAA/ASHRAE) | 18°F |
| 1% cooling design temperature (NOAA/ASHRAE) | 91°F |
| Mean coincident wet bulb | 74°F |
| Design grains (75°F, 50% RH indoors) | 34 |
| Daily range | Medium (July average 16°F) |
| IECC climate zone | 4A (Philadelphia County, 2021 IECC) |
| Nearby station | Northeast Philadelphia Airport (KPNE): 17°F heating, 91°F cooling |
With Manual J’s default indoor conditions of 70°F in winter and 75°F in summer, the heating load is driven by a 52°F difference and the cooling load by a 16°F difference, before sun, people and moisture are added. 34 design grains means a real latent load on top of the sensible load, so the equipment has to dehumidify as well as cool.
What drives loads in Philadelphia
NOAA lists Philadelphia International at 91°F cooling and 18°F heating, with 34 design grains. Northeast Philadelphia is 91°F and 17°F.
Much of the housing is older masonry with little insulation and heat that was originally from radiators. Adding central air or a heat pump means fitting ducts or going ductless, and the house's leakage often dominates the winter load.
Typical loads for Philadelphia homes
Four illustrative houses, each with 8-foot ceilings and ducts in the basement unless noted, at the design conditions above:
| House | Heating load | Cooling load | Nominal size | Sq ft per ton |
|---|---|---|---|---|
| Older 1,500 sq ft one-story fair insulation, double-pane windows | 40,953 Btuh | 27,085 Btuh | 2.5 tons | 665 |
| 2,000 sq ft one-story, built to code good insulation, low-E windows | 34,640 Btuh | 24,383 Btuh | 2.5 tons | 984 |
| 2,600 sq ft two-story, built to code good insulation, low-E windows | 38,672 Btuh | 28,078 Btuh | 2.5 tons | 1,111 |
| 2,000 sq ft high-performance excellent insulation and air sealing, ducts inside | 26,813 Btuh | 21,471 Btuh | 2 tons | 1,118 |
The spread is the point. The older 1,500 sq ft house needs 40,953 Btuh of heat, more than the 2,000 sq ft high-performance house at 26,813 Btuh, despite being 500 sq ft smaller. No square-foot rule can see that. These are whole-house block loads from the same engine the free Manual J calculator and the app use; a room-by-room load for a real house will differ.
Common sizing mistakes in Philadelphia
- Sizing a new ducted system to the old boiler's output. Boilers were often heavily oversized.
- Treating a rowhome like a detached house. Party walls cut the load substantially.
- Leaving out the third-floor and roof loads, where most of the summer heat comes in.
Heat pumps in Philadelphia
Heat pumps, including ductless ones, are a common upgrade path for Philadelphia rowhomes. At 18°F, check the unit's capacity at that temperature and keep backup heat for the gap. The cold-climate heat pump guide walks through capacity at the design temperature, the balance point and backup heat.
Run a load for your Philadelphia house
The free Manual J calculator takes a ZIP code and eight inputs and returns a whole-house heating and cooling load in the browser. The HVAC Load Calculator app goes further at the house: room-by-room loads, Manual S equipment sizes and a PDF report.
FAQ
Can I size a heat pump from my old boiler in Philadelphia?
No. Old boilers were often far bigger than the heat loss, and many houses have since had windows or insulation upgraded. Run a Manual J heat loss at the 18°F design temperature instead.
What is the Manual J design temperature for Philadelphia, PA?
NOAA’s Engineering Weather Data lists Philadelphia International Airport at 18°F for the 99% heating design and 91°F for the 1% cooling design, with a 74°F mean coincident wet bulb, from 1988–2017 observations. Use the station closest to the house in climate, and any value your building department requires.
What size AC do I need for a 2,000 sq ft house in Philadelphia?
It depends on the house, not the floor area. In our example, a code-built 2,000 sq ft one-story with low-E windows and ducts in the basement comes out at about 24,383 Btuh of cooling, a 2.5-ton nominal size, or about 984 sq ft per ton. An older or leakier house needs more; run a load for the actual house.