Scope. Outdoor design conditions and illustrative block loads for homes in and around Atlanta, GA. The example loads are estimates for typical houses, not a design for yours. Your building department may require specific design values. Not ACCA approved or certified, and not a stamped design.

Atlanta design conditions

Weather stationHartsfield-Jackson Atlanta International Airport (KATL)
SourceNOAA NCEI Engineering Weather Data, 1988–2017 observations
Elevation1,026 ft
99% heating design temperature (NOAA/ASHRAE)27°F
1% cooling design temperature (NOAA/ASHRAE)91°F
Mean coincident wet bulb74°F
Design grains (75°F, 50% RH indoors)34
Daily rangeMedium (July average 17°F)
IECC climate zone3A (Fulton County, 2021 IECC)

With Manual J’s default indoor conditions of 70°F in winter and 75°F in summer, the heating load is driven by a 43°F difference and the cooling load by a 16°F difference, before sun, people and moisture are added. 34 design grains means a real latent load on top of the sensible load, so the equipment has to dehumidify as well as cool.

What drives loads in Atlanta

NOAA lists Hartsfield-Jackson at 91°F cooling and 27°F heating, with 34 design grains.

Housing varies more than most metros: older homes on crawlspaces or basements, newer two-stories with attic ducts. Where the ducts run changes the result as much as the square footage does.

Typical loads for Atlanta homes

Four illustrative houses, each with 8-foot ceilings and ducts in a vented attic unless noted, at the design conditions above:

HouseHeating loadCooling loadNominal sizeSq ft per ton
Older 1,500 sq ft one-story
fair insulation, double-pane windows
37,243 Btuh29,202 Btuh2.5 tons616
2,000 sq ft one-story, built to code
good insulation, low-E windows
31,693 Btuh26,339 Btuh2.5 tons911
2,600 sq ft two-story, built to code
good insulation, low-E windows
35,244 Btuh30,313 Btuh3 tons1,029
2,000 sq ft high-performance
excellent insulation and air sealing, ducts inside
22,568 Btuh21,368 Btuh2 tons1,123

The spread is the point. The older 1,500 sq ft house needs 37,243 Btuh of heat, more than the 2,000 sq ft high-performance house at 22,568 Btuh, despite being 500 sq ft smaller. No square-foot rule can see that. These are whole-house block loads from the same engine the free Manual J calculator and the app use; a room-by-room load for a real house will differ.

Common sizing mistakes in Atlanta

  • Assuming the old 3.5-ton system was right. Many Atlanta homes were oversized, then got new windows and attic insulation.
  • Leaving crawlspace ducts out of the duct-loss inputs. A vented crawlspace in January is cold; in July it is damp.
  • Using one design temperature for the whole metro. North-side suburbs at higher elevation are a few degrees colder.

Heat pumps in Atlanta

Heat pumps work well in Atlanta. At 27°F a standard unit is below its rated capacity, so read the 17°F data, find the balance point and size the backup heat for the difference. The heat pump sizing guide covers reading capacity at 47°F and 17°F and setting the balance point.

Run a load for your Atlanta house

The free Manual J calculator takes a ZIP code and eight inputs and returns a whole-house heating and cooling load in the browser. The HVAC Load Calculator app goes further at the house: room-by-room loads, Manual S equipment sizes and a PDF report.

FAQ

Gas furnace or heat pump in Atlanta?

Both are common. A heat pump covers most Atlanta heating hours efficiently; a dual-fuel setup adds a gas furnace for the coldest nights. Either way, size from the Manual J heat loss at 27°F.

What is the Manual J design temperature for Atlanta, GA?

NOAA’s Engineering Weather Data lists Hartsfield-Jackson Atlanta International Airport at 27°F for the 99% heating design and 91°F for the 1% cooling design, with a 74°F mean coincident wet bulb, from 1988–2017 observations. Use the station closest to the house in climate, and any value your building department requires.

What size AC do I need for a 2,000 sq ft house in Atlanta?

It depends on the house, not the floor area. In our example, a code-built 2,000 sq ft one-story with low-E windows and ducts in a vented attic comes out at about 26,339 Btuh of cooling, a 2.5-ton nominal size, or about 911 sq ft per ton. An older or leakier house needs more; run a load for the actual house.