Scope. Outdoor design conditions and illustrative block loads for homes in and around Atlanta, GA. The example loads are estimates for typical houses, not a design for yours. Your building department may require specific design values. Not ACCA approved or certified, and not a stamped design.
Atlanta design conditions
| Weather station | Hartsfield-Jackson Atlanta International Airport (KATL) |
|---|---|
| Source | NOAA NCEI Engineering Weather Data, 1988–2017 observations |
| Elevation | 1,026 ft |
| 99% heating design temperature (NOAA/ASHRAE) | 27°F |
| 1% cooling design temperature (NOAA/ASHRAE) | 91°F |
| Mean coincident wet bulb | 74°F |
| Design grains (75°F, 50% RH indoors) | 34 |
| Daily range | Medium (July average 17°F) |
| IECC climate zone | 3A (Fulton County, 2021 IECC) |
With Manual J’s default indoor conditions of 70°F in winter and 75°F in summer, the heating load is driven by a 43°F difference and the cooling load by a 16°F difference, before sun, people and moisture are added. 34 design grains means a real latent load on top of the sensible load, so the equipment has to dehumidify as well as cool.
What drives loads in Atlanta
NOAA lists Hartsfield-Jackson at 91°F cooling and 27°F heating, with 34 design grains.
Housing varies more than most metros: older homes on crawlspaces or basements, newer two-stories with attic ducts. Where the ducts run changes the result as much as the square footage does.
Typical loads for Atlanta homes
Four illustrative houses, each with 8-foot ceilings and ducts in a vented attic unless noted, at the design conditions above:
| House | Heating load | Cooling load | Nominal size | Sq ft per ton |
|---|---|---|---|---|
| Older 1,500 sq ft one-story fair insulation, double-pane windows | 37,243 Btuh | 29,202 Btuh | 2.5 tons | 616 |
| 2,000 sq ft one-story, built to code good insulation, low-E windows | 31,693 Btuh | 26,339 Btuh | 2.5 tons | 911 |
| 2,600 sq ft two-story, built to code good insulation, low-E windows | 35,244 Btuh | 30,313 Btuh | 3 tons | 1,029 |
| 2,000 sq ft high-performance excellent insulation and air sealing, ducts inside | 22,568 Btuh | 21,368 Btuh | 2 tons | 1,123 |
The spread is the point. The older 1,500 sq ft house needs 37,243 Btuh of heat, more than the 2,000 sq ft high-performance house at 22,568 Btuh, despite being 500 sq ft smaller. No square-foot rule can see that. These are whole-house block loads from the same engine the free Manual J calculator and the app use; a room-by-room load for a real house will differ.
Common sizing mistakes in Atlanta
- Assuming the old 3.5-ton system was right. Many Atlanta homes were oversized, then got new windows and attic insulation.
- Leaving crawlspace ducts out of the duct-loss inputs. A vented crawlspace in January is cold; in July it is damp.
- Using one design temperature for the whole metro. North-side suburbs at higher elevation are a few degrees colder.
Heat pumps in Atlanta
Heat pumps work well in Atlanta. At 27°F a standard unit is below its rated capacity, so read the 17°F data, find the balance point and size the backup heat for the difference. The heat pump sizing guide covers reading capacity at 47°F and 17°F and setting the balance point.
Run a load for your Atlanta house
The free Manual J calculator takes a ZIP code and eight inputs and returns a whole-house heating and cooling load in the browser. The HVAC Load Calculator app goes further at the house: room-by-room loads, Manual S equipment sizes and a PDF report.
FAQ
Gas furnace or heat pump in Atlanta?
Both are common. A heat pump covers most Atlanta heating hours efficiently; a dual-fuel setup adds a gas furnace for the coldest nights. Either way, size from the Manual J heat loss at 27°F.
What is the Manual J design temperature for Atlanta, GA?
NOAA’s Engineering Weather Data lists Hartsfield-Jackson Atlanta International Airport at 27°F for the 99% heating design and 91°F for the 1% cooling design, with a 74°F mean coincident wet bulb, from 1988–2017 observations. Use the station closest to the house in climate, and any value your building department requires.
What size AC do I need for a 2,000 sq ft house in Atlanta?
It depends on the house, not the floor area. In our example, a code-built 2,000 sq ft one-story with low-E windows and ducts in a vented attic comes out at about 26,339 Btuh of cooling, a 2.5-ton nominal size, or about 911 sq ft per ton. An older or leakier house needs more; run a load for the actual house.