Scope. Outdoor design conditions and illustrative block loads for homes in and around Dallas, TX. The example loads are estimates for typical houses, not a design for yours. Your building department may require specific design values. Not ACCA approved or certified, and not a stamped design.
Dallas design conditions
| Weather station | Dallas-Fort Worth International Airport (KDFW) |
|---|---|
| Source | NOAA NCEI Engineering Weather Data, 1988–2017 observations |
| Elevation | 607 ft |
| 99% heating design temperature (NOAA/ASHRAE) | 27°F |
| 1% cooling design temperature (NOAA/ASHRAE) | 99°F |
| Mean coincident wet bulb | 75°F |
| Design grains (75°F, 50% RH indoors) | 25 |
| Daily range | Medium (July average 19°F) |
| IECC climate zone | 2A (Dallas County, 2021 IECC) |
| Nearby station | Dallas Love Field (KDAL): 28°F heating, 99°F cooling |
With Manual J’s default indoor conditions of 70°F in winter and 75°F in summer, the heating load is driven by a 43°F difference and the cooling load by a 24°F difference, before sun, people and moisture are added. 25 design grains means a real latent load on top of the sensible load, so the equipment has to dehumidify as well as cool.
What drives loads in Dallas
NOAA lists DFW Airport at 99°F cooling and 27°F heating; Love Field, closer to the city, is 99°F and 28°F. Design grains are moderate at 25.
Typical North Texas homes are slab-on-grade with attic ducts and a gas furnace or heat pump. The winter design temperature is cold enough that the heating load can rival the cooling load in a leaky older house.
Typical loads for Dallas homes
Four illustrative houses, each with 8-foot ceilings and ducts in a vented attic unless noted, at the design conditions above:
| House | Heating load | Cooling load | Nominal size | Sq ft per ton |
|---|---|---|---|---|
| Older 1,500 sq ft one-story fair insulation, double-pane windows | 37,364 Btuh | 33,916 Btuh | 3 tons | 531 |
| 2,000 sq ft one-story, built to code good insulation, low-E windows | 31,780 Btuh | 29,819 Btuh | 2.5 tons | 805 |
| 2,600 sq ft two-story, built to code good insulation, low-E windows | 35,352 Btuh | 34,660 Btuh | 3 tons | 900 |
| 2,000 sq ft high-performance excellent insulation and air sealing, ducts inside | 22,622 Btuh | 23,496 Btuh | 2 tons | 1,021 |
The spread is the point. The older 1,500 sq ft house needs 37,364 Btuh of heat, more than the 2,000 sq ft high-performance house at 22,622 Btuh, despite being 500 sq ft smaller. No square-foot rule can see that. These are whole-house block loads from the same engine the free Manual J calculator and the app use; a room-by-room load for a real house will differ.
Common sizing mistakes in Dallas
- Assuming cooling is the only load. Run both sides; older Dallas homes can have a heating load close to their cooling load.
- Using the wrong code edition. Check which IECC your city adopted before relying on the climate zone for insulation or equipment rules.
- Matching the old system's size after a remodel that added insulation or replaced windows.
Heat pumps in Dallas
A standard heat pump covers most Dallas winter hours. At 27°F it delivers well below its rated capacity, so check the 17°F performance data and size backup heat for the gap. The heat pump sizing guide covers reading capacity at 47°F and 17°F and setting the balance point.
Run a load for your Dallas house
The free Manual J calculator takes a ZIP code and eight inputs and returns a whole-house heating and cooling load in the browser. The HVAC Load Calculator app goes further at the house: room-by-room loads, Manual S equipment sizes and a PDF report.
FAQ
What climate zone is Dallas?
Dallas County is zone 2A on the 2021 IECC map, moved from 3A on earlier maps. Many Texas jurisdictions adopt the IECC on their own schedule, so check which edition your city enforces.
What is the Manual J design temperature for Dallas, TX?
NOAA’s Engineering Weather Data lists Dallas-Fort Worth International Airport at 27°F for the 99% heating design and 99°F for the 1% cooling design, with a 75°F mean coincident wet bulb, from 1988–2017 observations. Use the station closest to the house in climate, and any value your building department requires.
What size AC do I need for a 2,000 sq ft house in Dallas?
It depends on the house, not the floor area. In our example, a code-built 2,000 sq ft one-story with low-E windows and ducts in a vented attic comes out at about 29,819 Btuh of cooling, a 2.5-ton nominal size, or about 805 sq ft per ton. An older or leakier house needs more; run a load for the actual house.