Scope. Outdoor design conditions and illustrative block loads for homes in and around New Orleans, LA. The example loads are estimates for typical houses, not a design for yours. Your building department may require specific design values. Not ACCA approved or certified, and not a stamped design.
New Orleans design conditions
| Weather station | Louis Armstrong New Orleans International Airport (KMSY) |
|---|---|
| Source | NOAA NCEI Engineering Weather Data, 1988–2017 observations |
| Elevation | 4 ft |
| 99% heating design temperature (NOAA/ASHRAE) | 36°F |
| 1% cooling design temperature (NOAA/ASHRAE) | 93°F |
| Mean coincident wet bulb | 78°F |
| Design grains (75°F, 50% RH indoors) | 55 |
| Daily range | Low (July average 15°F) |
| IECC climate zone | 2A (Orleans Parish, 2021 IECC) |
| Nearby station | New Orleans Lakefront Airport (KNEW): 39°F heating, 92°F cooling |
With Manual J’s default indoor conditions of 70°F in winter and 75°F in summer, the heating load is driven by a 34°F difference and the cooling load by a 18°F difference, before sun, people and moisture are added. 55 design grains is a lot of moisture, so a large share of the cooling load is latent, water the coil has to remove.
What drives loads in New Orleans
NOAA lists Louis Armstrong International at 93°F cooling and 36°F heating, with 55 design grains. Lakefront Airport, on the lake, is milder in winter at 39°F. Summer nights stay warm and wet, so the system runs nearly around the clock.
Older homes here are often raised, with tall ceilings, lots of windows and ductwork added later in attics. Tall ceilings raise the conditioned volume, and leaky raised floors bring in outside air.
Typical loads for New Orleans homes
Four illustrative houses, each with 8-foot ceilings and ducts in a vented attic unless noted, at the design conditions above:
| House | Heating load | Cooling load | Nominal size | Sq ft per ton |
|---|---|---|---|---|
| Older 1,500 sq ft one-story fair insulation, double-pane windows | 30,324 Btuh | 33,373 Btuh | 3 tons | 539 |
| 2,000 sq ft one-story, built to code good insulation, low-E windows | 25,949 Btuh | 29,789 Btuh | 2.5 tons | 806 |
| 2,600 sq ft two-story, built to code good insulation, low-E windows | 28,747 Btuh | 34,401 Btuh | 3 tons | 907 |
| 2,000 sq ft high-performance excellent insulation and air sealing, ducts inside | 18,626 Btuh | 23,851 Btuh | 2 tons | 1,006 |
The spread is the point. The older 1,500 sq ft house needs 30,324 Btuh of heat, more than the 2,000 sq ft high-performance house at 18,626 Btuh, despite being 500 sq ft smaller. No square-foot rule can see that. These are whole-house block loads from the same engine the free Manual J calculator and the app use; a room-by-room load for a real house will differ.
Common sizing mistakes in New Orleans
- Treating a 12-foot ceiling like an 8-foot one. Enter the real ceiling height; volume matters for infiltration.
- Oversizing to fight humidity. A bigger system dehumidifies less, not more.
- Leaving duct leakage out of an attic retrofit. Return leaks in particular pull humid attic air into the house.
Heat pumps in New Orleans
A heat pump covers New Orleans winters easily. Choose it for cooling and moisture: variable-speed equipment or a dedicated dehumidifier often does more for comfort than added tonnage. The heat pump sizing guide covers reading capacity at 47°F and 17°F and setting the balance point.
Run a load for your New Orleans house
The free Manual J calculator takes a ZIP code and eight inputs and returns a whole-house heating and cooling load in the browser. The HVAC Load Calculator app goes further at the house: room-by-room loads, Manual S equipment sizes and a PDF report.
FAQ
Why does my New Orleans house feel damp even with the AC on?
Usually the system is oversized or running too much airflow, so the coil never gets cold enough for long enough to remove moisture. With 55 design grains, latent load is a large share of the total; a Manual J shows whether the equipment is matched to it.
What is the Manual J design temperature for New Orleans, LA?
NOAA’s Engineering Weather Data lists Louis Armstrong New Orleans International Airport at 36°F for the 99% heating design and 93°F for the 1% cooling design, with a 78°F mean coincident wet bulb, from 1988–2017 observations. Use the station closest to the house in climate, and any value your building department requires.
What size AC do I need for a 2,000 sq ft house in New Orleans?
It depends on the house, not the floor area. In our example, a code-built 2,000 sq ft one-story with low-E windows and ducts in a vented attic comes out at about 29,789 Btuh of cooling, a 2.5-ton nominal size, or about 806 sq ft per ton. An older or leakier house needs more; run a load for the actual house.