Scope. Outdoor design conditions and illustrative block loads for homes in and around Orlando, FL. The example loads are estimates for typical houses, not a design for yours. Your building department may require specific design values. Not ACCA approved or certified, and not a stamped design.

Orlando design conditions

Weather stationOrlando International Airport (KMCO)
SourceNOAA NCEI Engineering Weather Data, 1988–2017 observations
Elevation96 ft
99% heating design temperature (NOAA/ASHRAE)43°F
1% cooling design temperature (NOAA/ASHRAE)92°F
Mean coincident wet bulb76°F
Design grains (75°F, 50% RH indoors)46
Daily rangeMedium (July average 17°F)
IECC climate zone2A (Orange County, 2021 IECC)

With Manual J’s default indoor conditions of 70°F in winter and 75°F in summer, the heating load is driven by a 27°F difference and the cooling load by a 17°F difference, before sun, people and moisture are added. 46 design grains is a lot of moisture, so a large share of the cooling load is latent, water the coil has to remove.

What drives loads in Orlando

The airport station puts the 1% cooling design temperature at 92°F with 46 design grains, and a medium daily range, so evenings cool off more than in Tampa or Miami. That swing slightly lowers the cooling load compared with a coastal house of the same build.

Typical Orlando homes are slab-on-grade with ducts and air handlers in a vented attic or garage. Afternoon sun on west glass and attic duct gain set the peak more than the outdoor temperature itself.

Typical loads for Orlando homes

Four illustrative houses, each with 8-foot ceilings and ducts in a vented attic unless noted, at the design conditions above:

HouseHeating loadCooling loadNominal sizeSq ft per ton
Older 1,500 sq ft one-story
fair insulation, double-pane windows
24,916 Btuh31,100 Btuh3 tons579
2,000 sq ft one-story, built to code
good insulation, low-E windows
21,446 Btuh27,960 Btuh2.5 tons858
2,600 sq ft two-story, built to code
good insulation, low-E windows
23,667 Btuh32,215 Btuh3 tons968
2,000 sq ft high-performance
excellent insulation and air sealing, ducts inside
15,525 Btuh22,598 Btuh2 tons1,062

The spread is the point. The older 1,500 sq ft house needs 24,916 Btuh of heat, more than the 2,000 sq ft high-performance house at 15,525 Btuh, despite being 500 sq ft smaller. No square-foot rule can see that. These are whole-house block loads from the same engine the free Manual J calculator and the app use; a room-by-room load for a real house will differ.

Common sizing mistakes in Orlando

  • Sizing by square feet. Orlando's newer subdivisions are built to a much tighter code than the homes the rules of thumb came from.
  • Forgetting the coincident wet bulb. The 76°F wet bulb is what drives the latent load; leaving it at a default understates moisture.
  • Treating the bonus room over the garage like the rest of the house. It usually has the worst load per square foot and needs its own airflow.

Heat pumps in Orlando

Heat pumps are standard in Orlando, and the 43°F heating design temperature is well inside any heat pump's comfortable range. Pick equipment for cooling and dehumidification. The heat pump sizing guide covers reading capacity at 47°F and 17°F and setting the balance point.

Run a load for your Orlando house

The free Manual J calculator takes a ZIP code and eight inputs and returns a whole-house heating and cooling load in the browser. The HVAC Load Calculator app goes further at the house: room-by-room loads, Manual S equipment sizes and a PDF report.

FAQ

Is Orlando's design temperature different from the rest of Florida?

Yes. NOAA lists Orlando International at 43°F heating and 92°F cooling, versus 53°F and 91°F at Miami International. Inland Florida swings more between day and night, and the numbers reflect that.

What is the Manual J design temperature for Orlando, FL?

NOAA’s Engineering Weather Data lists Orlando International Airport at 43°F for the 99% heating design and 92°F for the 1% cooling design, with a 76°F mean coincident wet bulb, from 1988–2017 observations. Use the station closest to the house in climate, and any value your building department requires.

What size AC do I need for a 2,000 sq ft house in Orlando?

It depends on the house, not the floor area. In our example, a code-built 2,000 sq ft one-story with low-E windows and ducts in a vented attic comes out at about 27,960 Btuh of cooling, a 2.5-ton nominal size, or about 858 sq ft per ton. An older or leakier house needs more; run a load for the actual house.