Scope. Outdoor design conditions and illustrative block loads for homes in and around Los Angeles, CA. The example loads are estimates for typical houses, not a design for yours. Your building department may require specific design values. Not ACCA approved or certified, and not a stamped design.

Los Angeles design conditions

Weather stationLos Angeles International Airport (KLAX)
SourceNOAA NCEI Engineering Weather Data, 1988–2017 observations
Elevation126 ft
99% heating design temperature (NOAA/ASHRAE)46°F
1% cooling design temperature (NOAA/ASHRAE)81°F
Mean coincident wet bulb64°F
Design grains (75°F, 50% RH indoors)-2
Daily rangeLow (July average 10°F)
IECC climate zone3B (Los Angeles County, 2021 IECC)
Nearby stationMarch ARB (Riverside, Inland Empire) (KRIV): 35°F heating, 99°F cooling

With Manual J’s default indoor conditions of 70°F in winter and 75°F in summer, the heating load is driven by a 24°F difference and the cooling load by a 6°F difference, before sun, people and moisture are added. Design grains are negative, which means the outdoor air at the design condition is drier than the indoor target: the cooling load is almost entirely sensible.

What drives loads in Los Angeles

NOAA lists Los Angeles International (LAX) on the coast at 81°F cooling and 46°F heating, with a low daily range. March ARB in the Inland Empire is 99°F and 35°F. Downtown and the San Fernando and San Gabriel valleys fall between the two or run hotter, so use the station that matches the house.

Many older LA homes were built without central air. Retrofits often add ducts in a hot attic or go ductless, and both choices change the cooling load as much as the climate does.

Typical loads for Los Angeles homes

Four illustrative houses, each with 8-foot ceilings and ducts in a vented attic unless noted, at the design conditions above:

HouseHeating loadCooling loadNominal sizeSq ft per ton
Older 1,500 sq ft one-story
fair insulation, double-pane windows
22,762 Btuh19,602 Btuh2 tons918
2,000 sq ft one-story, built to code
good insulation, low-E windows
19,625 Btuh18,510 Btuh2 tons1,297
2,600 sq ft two-story, built to code
good insulation, low-E windows
21,630 Btuh20,926 Btuh2 tons1,491
2,000 sq ft high-performance
excellent insulation and air sealing, ducts inside
14,253 Btuh15,758 Btuh1.5 tons1,523

The spread is the point. The older 1,500 sq ft house needs 22,762 Btuh of heat, more than the 2,000 sq ft high-performance house at 14,253 Btuh, despite being 500 sq ft smaller. No square-foot rule can see that. These are whole-house block loads from the same engine the free Manual J calculator and the app use; a room-by-room load for a real house will differ.

Common sizing mistakes in Los Angeles

  • Using the LAX number for a valley house. A coastal design temperature can understate an inland cooling load by a ton or more.
  • Sizing a retrofit to a quote's square-foot rule instead of the house's actual glass, insulation and shading.
  • Ignoring the attic. New ducts in an uninsulated attic add a large load.

Heat pumps in Los Angeles

Heat pumps suit LA well; the heating design temperatures are mild everywhere in the basin. Ductless heat pumps are a strong option for older homes without ducts. The heat pump sizing guide covers reading capacity at 47°F and 17°F and setting the balance point.

Run a load for your Los Angeles house

The free Manual J calculator takes a ZIP code and eight inputs and returns a whole-house heating and cooling load in the browser. The HVAC Load Calculator app goes further at the house: room-by-room loads, Manual S equipment sizes and a PDF report.

FAQ

Which design temperature should I use in Los Angeles?

The weather station closest to the house in climate. LAX on the coast is 81°F cooling, inland March ARB is 99°F, and downtown and the valleys fall between the two or run hotter. California also has its own Title 24 rules; check what your building department expects.

What is the Manual J design temperature for Los Angeles, CA?

NOAA’s Engineering Weather Data lists Los Angeles International Airport at 46°F for the 99% heating design and 81°F for the 1% cooling design, with a 64°F mean coincident wet bulb, from 1988–2017 observations. Use the station closest to the house in climate, and any value your building department requires.

What size AC do I need for a 2,000 sq ft house in Los Angeles?

It depends on the house, not the floor area. In our example, a code-built 2,000 sq ft one-story with low-E windows and ducts in a vented attic comes out at about 18,510 Btuh of cooling, a 2-ton nominal size, or about 1,297 sq ft per ton. An older or leakier house needs more; run a load for the actual house.