Scope. Outdoor design conditions and illustrative block loads for homes in and around Seattle, WA. The example loads are estimates for typical houses, not a design for yours. Your building department may require specific design values. Not ACCA approved or certified, and not a stamped design.
Seattle design conditions
| Weather station | Seattle-Tacoma International Airport (KSEA) |
|---|---|
| Source | NOAA NCEI Engineering Weather Data, 1988–2017 observations |
| Elevation | 433 ft |
| 99% heating design temperature (NOAA/ASHRAE) | 30°F |
| 1% cooling design temperature (NOAA/ASHRAE) | 82°F |
| Mean coincident wet bulb | 64°F |
| Design grains (75°F, 50% RH indoors) | -5 |
| Daily range | Medium (July average 19°F) |
| IECC climate zone | 4C (King County, 2021 IECC) |
| Nearby station | Boeing Field (KBFI): 29°F heating, 82°F cooling |
With Manual J’s default indoor conditions of 70°F in winter and 75°F in summer, the heating load is driven by a 40°F difference and the cooling load by a 7°F difference, before sun, people and moisture are added. Design grains are negative, which means the outdoor air at the design condition is drier than the indoor target: the cooling load is almost entirely sensible.
What drives loads in Seattle
NOAA lists Seattle-Tacoma International at 82°F cooling and 30°F heating, with negative design grains. Boeing Field is 82°F and 29°F. The heating design temperature is mild, but the heating season is long.
Older homes with crawlspaces and little insulation are common, alongside tight new construction. Most of the annual energy goes to heating, so the heat loss is the number to get right.
Typical loads for Seattle homes
Four illustrative houses, each with 8-foot ceilings and ducts in a vented crawlspace unless noted, at the design conditions above:
| House | Heating load | Cooling load | Nominal size | Sq ft per ton |
|---|---|---|---|---|
| Older 1,500 sq ft one-story fair insulation, double-pane windows | 33,809 Btuh | 18,822 Btuh | 2 tons | 956 |
| 2,000 sq ft one-story, built to code good insulation, low-E windows | 28,750 Btuh | 17,694 Btuh | 1.5 tons | 1,356 |
| 2,600 sq ft two-story, built to code good insulation, low-E windows | 31,981 Btuh | 20,043 Btuh | 2 tons | 1,557 |
| 2,000 sq ft high-performance excellent insulation and air sealing, ducts inside | 21,405 Btuh | 15,560 Btuh | 1.5 tons | 1,542 |
The spread is the point. The older 1,500 sq ft house needs 33,809 Btuh of heat, more than the 2,000 sq ft high-performance house at 21,405 Btuh, despite being 500 sq ft smaller. No square-foot rule can see that. These are whole-house block loads from the same engine the free Manual J calculator and the app use; a room-by-room load for a real house will differ.
Common sizing mistakes in Seattle
- Sizing a new heat pump to the June 2021 heat wave. Size to the design temperature; extremes are rare.
- Leaving the crawlspace out of the duct inputs.
- Assuming cooling is irrelevant. West-facing glass in a tight house can overheat quickly.
Heat pumps in Seattle
Seattle is close to ideal heat pump territory. A 30°F design temperature is easy for most equipment; size to the heating load and the cooling side usually comes along. The heat pump sizing guide covers reading capacity at 47°F and 17°F and setting the balance point.
Run a load for your Seattle house
The free Manual J calculator takes a ZIP code and eight inputs and returns a whole-house heating and cooling load in the browser. The HVAC Load Calculator app goes further at the house: room-by-room loads, Manual S equipment sizes and a PDF report.
FAQ
Should I size a Seattle heat pump for heating or cooling?
Heating. At 30°F and 82°F design temperatures, the heat loss is almost always larger than the cooling load. Pick a heat pump whose capacity at the design temperature covers the heat loss.
What is the Manual J design temperature for Seattle, WA?
NOAA’s Engineering Weather Data lists Seattle-Tacoma International Airport at 30°F for the 99% heating design and 82°F for the 1% cooling design, with a 64°F mean coincident wet bulb, from 1988–2017 observations. Use the station closest to the house in climate, and any value your building department requires.
What size AC do I need for a 2,000 sq ft house in Seattle?
It depends on the house, not the floor area. In our example, a code-built 2,000 sq ft one-story with low-E windows and ducts in a vented crawlspace comes out at about 17,694 Btuh of cooling, a 1.5-ton nominal size, or about 1,356 sq ft per ton. An older or leakier house needs more; run a load for the actual house.