Scope. Outdoor design conditions and illustrative block loads for homes in and around New York, NY. The example loads are estimates for typical houses, not a design for yours. Your building department may require specific design values. Not ACCA approved or certified, and not a stamped design.
New York design conditions
| Weather station | LaGuardia Airport (KLGA) |
|---|---|
| Source | NOAA NCEI Engineering Weather Data, 1988–2017 observations |
| Elevation | 22 ft |
| 99% heating design temperature (NOAA/ASHRAE) | 18°F |
| 1% cooling design temperature (NOAA/ASHRAE) | 90°F |
| Mean coincident wet bulb | 73°F |
| Design grains (75°F, 50% RH indoors) | 29 |
| Daily range | Low (July average 14°F) |
| IECC climate zone | 4A (New York County, 2021 IECC) |
With Manual J’s default indoor conditions of 70°F in winter and 75°F in summer, the heating load is driven by a 52°F difference and the cooling load by a 15°F difference, before sun, people and moisture are added. 29 design grains means a real latent load on top of the sensible load, so the equipment has to dehumidify as well as cool.
What drives loads in New York
NOAA lists LaGuardia at 90°F cooling and 18°F heating, with 29 design grains. Long Island and the northern suburbs have their own stations.
Brownstones and row houses share party walls, and apartments may have only one or two exterior walls. Large old windows, high ceilings and radiator heat are the norm, which changes both loads and the choice of equipment.
Typical loads for New York homes
Four illustrative houses, each with 8-foot ceilings and ducts in the basement unless noted, at the design conditions above:
| House | Heating load | Cooling load | Nominal size | Sq ft per ton |
|---|---|---|---|---|
| Older 1,500 sq ft one-story fair insulation, double-pane windows | 40,958 Btuh | 26,425 Btuh | 2.5 tons | 681 |
| 2,000 sq ft one-story, built to code good insulation, low-E windows | 34,643 Btuh | 23,801 Btuh | 2 tons | 1,008 |
| 2,600 sq ft two-story, built to code good insulation, low-E windows | 38,676 Btuh | 27,390 Btuh | 2.5 tons | 1,139 |
| 2,000 sq ft high-performance excellent insulation and air sealing, ducts inside | 26,815 Btuh | 20,944 Btuh | 2 tons | 1,146 |
The spread is the point. The older 1,500 sq ft house needs 40,958 Btuh of heat, more than the 2,000 sq ft high-performance house at 26,815 Btuh, despite being 500 sq ft smaller. No square-foot rule can see that. These are whole-house block loads from the same engine the free Manual J calculator and the app use; a room-by-room load for a real house will differ.
Common sizing mistakes in New York
- Treating an apartment like a house. Only walls, windows and ceilings to outdoors or unconditioned space count.
- Sizing window units or mini-splits by the square foot instead of each room's actual exposure.
- Ignoring the top floor. Roof gain makes it the hardest room to cool.
Heat pumps in New York
Ductless heat pumps are a natural fit for buildings without ducts. A 18°F design temperature is within reach of cold-climate models; check capacity at that temperature, not just the rating. The cold-climate heat pump guide walks through capacity at the design temperature, the balance point and backup heat.
Run a load for your New York house
The free Manual J calculator takes a ZIP code and eight inputs and returns a whole-house heating and cooling load in the browser. The HVAC Load Calculator app goes further at the house: room-by-room loads, Manual S equipment sizes and a PDF report.
FAQ
How do I size a mini-split for a New York apartment?
Run a room-by-room load with only the exterior walls and windows that apply, at LaGuardia's 90°F and 18°F design temperatures. Corner rooms and top floors will need noticeably more than interior rooms.
What is the Manual J design temperature for New York, NY?
NOAA’s Engineering Weather Data lists LaGuardia Airport at 18°F for the 99% heating design and 90°F for the 1% cooling design, with a 73°F mean coincident wet bulb, from 1988–2017 observations. Use the station closest to the house in climate, and any value your building department requires.
What size AC do I need for a 2,000 sq ft house in New York?
It depends on the house, not the floor area. In our example, a code-built 2,000 sq ft one-story with low-E windows and ducts in the basement comes out at about 23,801 Btuh of cooling, a 2-ton nominal size, or about 1,008 sq ft per ton. An older or leakier house needs more; run a load for the actual house.