Scope. Outdoor design conditions and illustrative block loads for homes in and around San Antonio, TX. The example loads are estimates for typical houses, not a design for yours. Your building department may require specific design values. Not ACCA approved or certified, and not a stamped design.
San Antonio design conditions
| Weather station | San Antonio International Airport (KSAT) |
|---|---|
| Source | NOAA NCEI Engineering Weather Data, 1988–2017 observations |
| Elevation | 809 ft |
| 99% heating design temperature (NOAA/ASHRAE) | 33°F |
| 1% cooling design temperature (NOAA/ASHRAE) | 97°F |
| Mean coincident wet bulb | 74°F |
| Design grains (75°F, 50% RH indoors) | 25 |
| Daily range | Medium (July average 19°F) |
| IECC climate zone | 2A (Bexar County, 2021 IECC) |
With Manual J’s default indoor conditions of 70°F in winter and 75°F in summer, the heating load is driven by a 37°F difference and the cooling load by a 22°F difference, before sun, people and moisture are added. 25 design grains means a real latent load on top of the sensible load, so the equipment has to dehumidify as well as cool.
What drives loads in San Antonio
NOAA lists San Antonio International at 97°F cooling and 33°F heating, with 25 design grains, well below Houston's 45. The air still needs drying in spring and after storms, but at the design condition most of the load is sensible.
Many homes are single-story on a slab with long attic duct runs. With 97°F outdoors the attic runs far hotter, so duct insulation and leakage show up directly in the result.
Typical loads for San Antonio homes
Four illustrative houses, each with 8-foot ceilings and ducts in a vented attic unless noted, at the design conditions above:
| House | Heating load | Cooling load | Nominal size | Sq ft per ton |
|---|---|---|---|---|
| Older 1,500 sq ft one-story fair insulation, double-pane windows | 32,438 Btuh | 32,301 Btuh | 3 tons | 557 |
| 2,000 sq ft one-story, built to code good insulation, low-E windows | 27,728 Btuh | 28,597 Btuh | 2.5 tons | 839 |
| 2,600 sq ft two-story, built to code good insulation, low-E windows | 30,743 Btuh | 33,151 Btuh | 3 tons | 941 |
| 2,000 sq ft high-performance excellent insulation and air sealing, ducts inside | 19,861 Btuh | 22,711 Btuh | 2 tons | 1,057 |
The spread is the point. The older 1,500 sq ft house needs 32,438 Btuh of heat, more than the 2,000 sq ft high-performance house at 19,861 Btuh, despite being 500 sq ft smaller. No square-foot rule can see that. These are whole-house block loads from the same engine the free Manual J calculator and the app use; a room-by-room load for a real house will differ.
Common sizing mistakes in San Antonio
- Using a coastal Texas station. San Antonio is drier and hotter than Houston and Corpus Christi.
- Picking equipment from the nominal tonnage alone. Check the condenser's capacity at 95–100°F outdoor, where it delivers less than its rating.
- Skipping the shade and orientation inputs on the west side of the house.
Heat pumps in San Antonio
A heat pump handles San Antonio's heating load easily. Freeze events below the design temperature are short; strip heat or a small furnace covers them without oversizing the cooling side. The heat pump sizing guide covers reading capacity at 47°F and 17°F and setting the balance point.
Run a load for your San Antonio house
The free Manual J calculator takes a ZIP code and eight inputs and returns a whole-house heating and cooling load in the browser. The HVAC Load Calculator app goes further at the house: room-by-room loads, Manual S equipment sizes and a PDF report.
FAQ
Does San Antonio need high-SHR or low-SHR equipment?
At the design condition, the load is mostly sensible because the design grains are only 25. Equipment with a normal or higher sensible heat ratio fits, as long as it can still dehumidify in the swing seasons.
What is the Manual J design temperature for San Antonio, TX?
NOAA’s Engineering Weather Data lists San Antonio International Airport at 33°F for the 99% heating design and 97°F for the 1% cooling design, with a 74°F mean coincident wet bulb, from 1988–2017 observations. Use the station closest to the house in climate, and any value your building department requires.
What size AC do I need for a 2,000 sq ft house in San Antonio?
It depends on the house, not the floor area. In our example, a code-built 2,000 sq ft one-story with low-E windows and ducts in a vented attic comes out at about 28,597 Btuh of cooling, a 2.5-ton nominal size, or about 839 sq ft per ton. An older or leakier house needs more; run a load for the actual house.