Scope. Outdoor design conditions and illustrative block loads for homes in and around Houston, TX. The example loads are estimates for typical houses, not a design for yours. Your building department may require specific design values. Not ACCA approved or certified, and not a stamped design.

Houston design conditions

Weather stationGeorge Bush Intercontinental Airport (KIAH)
SourceNOAA NCEI Engineering Weather Data, 1988–2017 observations
Elevation97 ft
99% heating design temperature (NOAA/ASHRAE)34°F
1% cooling design temperature (NOAA/ASHRAE)95°F
Mean coincident wet bulb77°F
Design grains (75°F, 50% RH indoors)45
Daily rangeMedium (July average 18°F)
IECC climate zone2A (Harris County, 2021 IECC)

With Manual J’s default indoor conditions of 70°F in winter and 75°F in summer, the heating load is driven by a 36°F difference and the cooling load by a 20°F difference, before sun, people and moisture are added. 45 design grains is a lot of moisture, so a large share of the cooling load is latent, water the coil has to remove.

What drives loads in Houston

Bush Intercontinental's 1% cooling design temperature is 95°F with 45 design grains. Stations nearer the bay can differ, so pick the station closest to the house in climate, not just in distance.

Big two-story homes with ducts in hot attics are typical. The upstairs carries the attic and roof gain plus warm air rising, so a whole-house tonnage often hides an upstairs that is under-served and a downstairs that is over-cooled.

Typical loads for Houston homes

Four illustrative houses, each with 8-foot ceilings and ducts in a vented attic unless noted, at the design conditions above:

HouseHeating loadCooling loadNominal sizeSq ft per ton
Older 1,500 sq ft one-story
fair insulation, double-pane windows
31,841 Btuh33,288 Btuh3 tons541
2,000 sq ft one-story, built to code
good insulation, low-E windows
27,214 Btuh29,628 Btuh2.5 tons810
2,600 sq ft two-story, built to code
good insulation, low-E windows
30,175 Btuh34,271 Btuh3 tons910
2,000 sq ft high-performance
excellent insulation and air sealing, ducts inside
19,499 Btuh23,679 Btuh2 tons1,014

The spread is the point. The older 1,500 sq ft house needs 31,841 Btuh of heat, more than the 2,000 sq ft high-performance house at 19,499 Btuh, despite being 500 sq ft smaller. No square-foot rule can see that. These are whole-house block loads from the same engine the free Manual J calculator and the app use; a room-by-room load for a real house will differ.

Common sizing mistakes in Houston

  • Sizing to the hottest day you remember instead of the 1% design temperature. Manual J says not to add safety factors to the outdoor design conditions.
  • One system, two floors, no zoning or balancing. Run room-by-room loads so the upstairs gets the airflow it needs.
  • Ignoring attic duct leakage. In Houston it is both a cooling and a moisture load.

Heat pumps in Houston

Houston's 34°F heating design temperature is mild, so a heat pump or a small gas furnace both work. Size whichever you choose to the cooling load first and confirm it also covers the heat loss. The heat pump sizing guide covers reading capacity at 47°F and 17°F and setting the balance point.

Run a load for your Houston house

The free Manual J calculator takes a ZIP code and eight inputs and returns a whole-house heating and cooling load in the browser. The HVAC Load Calculator app goes further at the house: room-by-room loads, Manual S equipment sizes and a PDF report.

FAQ

Why is my upstairs always hotter in Houston?

The second floor takes the roof and attic gain, often has the most glass, and in many homes is fed by long attic duct runs. A room-by-room Manual J usually shows the upstairs needs a larger share of the airflow than it gets.

What is the Manual J design temperature for Houston, TX?

NOAA’s Engineering Weather Data lists George Bush Intercontinental Airport at 34°F for the 99% heating design and 95°F for the 1% cooling design, with a 77°F mean coincident wet bulb, from 1988–2017 observations. Use the station closest to the house in climate, and any value your building department requires.

What size AC do I need for a 2,000 sq ft house in Houston?

It depends on the house, not the floor area. In our example, a code-built 2,000 sq ft one-story with low-E windows and ducts in a vented attic comes out at about 29,628 Btuh of cooling, a 2.5-ton nominal size, or about 810 sq ft per ton. An older or leakier house needs more; run a load for the actual house.