Scope. Outdoor design conditions and illustrative block loads for homes in and around Boston, MA. The example loads are estimates for typical houses, not a design for yours. Your building department may require specific design values. Not ACCA approved or certified, and not a stamped design.
Boston design conditions
| Weather station | Logan International Airport (KBOS) |
|---|---|
| Source | NOAA NCEI Engineering Weather Data, 1988–2017 observations |
| Elevation | 20 ft |
| 99% heating design temperature (NOAA/ASHRAE) | 13°F |
| 1% cooling design temperature (NOAA/ASHRAE) | 88°F |
| Mean coincident wet bulb | 72°F |
| Design grains (75°F, 50% RH indoors) | 26 |
| Daily range | Low (July average 15°F) |
| IECC climate zone | 5A (Suffolk County, 2021 IECC) |
With Manual J’s default indoor conditions of 70°F in winter and 75°F in summer, the heating load is driven by a 57°F difference and the cooling load by a 13°F difference, before sun, people and moisture are added. 26 design grains means a real latent load on top of the sensible load, so the equipment has to dehumidify as well as cool.
What drives loads in Boston
NOAA lists Logan Airport at 88°F cooling and 13°F heating, with 26 design grains. Logan sits on the harbor; inland suburbs are colder, so use the station that matches the house.
Older homes with balloon framing, little insulation and radiator or baseboard heat are common. Converting to a heat pump means sizing the heat pump from a real heat loss, not from the boiler.
Typical loads for Boston homes
Four illustrative houses, each with 8-foot ceilings and ducts in the basement unless noted, at the design conditions above:
| House | Heating load | Cooling load | Nominal size | Sq ft per ton |
|---|---|---|---|---|
| Older 1,500 sq ft one-story fair insulation, double-pane windows | 45,917 Btuh | 24,854 Btuh | 2.5 tons | 724 |
| 2,000 sq ft one-story, built to code good insulation, low-E windows | 39,031 Btuh | 22,517 Btuh | 2 tons | 1,066 |
| 2,600 sq ft two-story, built to code good insulation, low-E windows | 43,295 Btuh | 25,837 Btuh | 2.5 tons | 1,208 |
| 2,000 sq ft high-performance excellent insulation and air sealing, ducts inside | 30,308 Btuh | 19,982 Btuh | 2 tons | 1,201 |
The spread is the point. The older 1,500 sq ft house needs 45,917 Btuh of heat, more than the 2,000 sq ft high-performance house at 30,308 Btuh, despite being 500 sq ft smaller. No square-foot rule can see that. These are whole-house block loads from the same engine the free Manual J calculator and the app use; a room-by-room load for a real house will differ.
Common sizing mistakes in Boston
- Sizing a heat pump from the boiler's rating. Old boilers are often far oversized.
- Using Logan's 13°F for an inland suburb that runs colder.
- Ignoring air leakage. In older Boston homes it can be the largest single heat loss.
Heat pumps in Boston
Cold-climate heat pumps are the standard upgrade path. At 13°F, check capacity at 5°F and 17°F and decide whether to keep the existing boiler or furnace as backup. The cold-climate heat pump guide walks through capacity at the design temperature, the balance point and backup heat.
Run a load for your Boston house
The free Manual J calculator takes a ZIP code and eight inputs and returns a whole-house heating and cooling load in the browser. The HVAC Load Calculator app goes further at the house: room-by-room loads, Manual S equipment sizes and a PDF report.
FAQ
Can a heat pump heat an older Boston home?
Often yes, if it is sized from a Manual J heat loss and is a cold-climate model with enough capacity at the 13°F design temperature. Air sealing first can shrink the equipment you need.
What is the Manual J design temperature for Boston, MA?
NOAA’s Engineering Weather Data lists Logan International Airport at 13°F for the 99% heating design and 88°F for the 1% cooling design, with a 72°F mean coincident wet bulb, from 1988–2017 observations. Use the station closest to the house in climate, and any value your building department requires.
What size AC do I need for a 2,000 sq ft house in Boston?
It depends on the house, not the floor area. In our example, a code-built 2,000 sq ft one-story with low-E windows and ducts in the basement comes out at about 22,517 Btuh of cooling, a 2-ton nominal size, or about 1,066 sq ft per ton. An older or leakier house needs more; run a load for the actual house.