Scope. Outdoor design conditions and illustrative block loads for homes in and around Phoenix, AZ. The example loads are estimates for typical houses, not a design for yours. Your building department may require specific design values. Not ACCA approved or certified, and not a stamped design.
Phoenix design conditions
| Weather station | Phoenix Sky Harbor International Airport (KPHX) |
|---|---|
| Source | NOAA NCEI Engineering Weather Data, 1988–2017 observations |
| Elevation | 1,135 ft |
| 99% heating design temperature (NOAA/ASHRAE) | 42°F |
| 1% cooling design temperature (NOAA/ASHRAE) | 108°F |
| Mean coincident wet bulb | 69°F |
| Design grains (75°F, 50% RH indoors) | -17 |
| Daily range | Medium (July average 21°F) |
| IECC climate zone | 2B (Maricopa County, 2021 IECC) |
| Nearby station | Luke AFB (west valley) (KLUF): 37°F heating, 109°F cooling |
With Manual J’s default indoor conditions of 70°F in winter and 75°F in summer, the heating load is driven by a 28°F difference and the cooling load by a 33°F difference, before sun, people and moisture are added. Design grains are negative, which means the outdoor air at the design condition is drier than the indoor target: the cooling load is almost entirely sensible.
What drives loads in Phoenix
NOAA lists Sky Harbor at 108°F cooling and 42°F heating, with negative design grains: at the design condition the outdoor air is drier than the indoor target, so the load is almost all sensible. Luke AFB in the west valley is 109°F and 37°F.
Attic ductwork is the hidden load. With ducts in a vented attic above a 108°F day, duct gain and leakage can add a large share to the room loads. Low-E glass and shading on west and south exposures make the next biggest difference.
Typical loads for Phoenix homes
Four illustrative houses, each with 8-foot ceilings and ducts in a vented attic unless noted, at the design conditions above:
| House | Heating load | Cooling load | Nominal size | Sq ft per ton |
|---|---|---|---|---|
| Older 1,500 sq ft one-story fair insulation, double-pane windows | 25,495 Btuh | 33,825 Btuh | 3 tons | 532 |
| 2,000 sq ft one-story, built to code good insulation, low-E windows | 21,948 Btuh | 29,194 Btuh | 2.5 tons | 822 |
| 2,600 sq ft two-story, built to code good insulation, low-E windows | 24,220 Btuh | 34,186 Btuh | 3 tons | 913 |
| 2,000 sq ft high-performance excellent insulation and air sealing, ducts inside | 15,879 Btuh | 22,660 Btuh | 2 tons | 1,059 |
The spread is the point. The older 1,500 sq ft house needs 25,495 Btuh of heat, more than the 2,000 sq ft high-performance house at 15,879 Btuh, despite being 500 sq ft smaller. No square-foot rule can see that. These are whole-house block loads from the same engine the free Manual J calculator and the app use; a room-by-room load for a real house will differ.
Common sizing mistakes in Phoenix
- Sizing to the record high instead of the 1% design temperature. Manual J does not add safety margins.
- Picking a condenser by its nominal tonnage. Air conditioners lose capacity as outdoor temperature rises; check the manufacturer's data at 105–115°F.
- Ignoring the monsoon. July and August bring humid days where an oversized system short-cycles and leaves the house muggy.
Heat pumps in Phoenix
Heat pumps are the default in Phoenix, and the 42°F heating design temperature is easy. Choose by cooling performance at high ambient temperatures. The heat pump sizing guide covers reading capacity at 47°F and 17°F and setting the balance point.
Run a load for your Phoenix house
The free Manual J calculator takes a ZIP code and eight inputs and returns a whole-house heating and cooling load in the browser. The HVAC Load Calculator app goes further at the house: room-by-room loads, Manual S equipment sizes and a PDF report.
FAQ
Why not size a Phoenix AC to 115°F?
Manual J uses the 1% design temperature, 108°F at Sky Harbor, and says not to add safety factors. Above that, a right-sized system runs continuously and the house drifts a degree or two for a few hours. Sizing for the extreme leaves you oversized for the rest of the summer.
What is the Manual J design temperature for Phoenix, AZ?
NOAA’s Engineering Weather Data lists Phoenix Sky Harbor International Airport at 42°F for the 99% heating design and 108°F for the 1% cooling design, with a 69°F mean coincident wet bulb, from 1988–2017 observations. Use the station closest to the house in climate, and any value your building department requires.
What size AC do I need for a 2,000 sq ft house in Phoenix?
It depends on the house, not the floor area. In our example, a code-built 2,000 sq ft one-story with low-E windows and ducts in a vented attic comes out at about 29,194 Btuh of cooling, a 2.5-ton nominal size, or about 822 sq ft per ton. An older or leakier house needs more; run a load for the actual house.