Scope. Outdoor design conditions and illustrative block loads for homes in and around Phoenix, AZ. The example loads are estimates for typical houses, not a design for yours. Your building department may require specific design values. Not ACCA approved or certified, and not a stamped design.

Phoenix design conditions

Weather stationPhoenix Sky Harbor International Airport (KPHX)
SourceNOAA NCEI Engineering Weather Data, 1988–2017 observations
Elevation1,135 ft
99% heating design temperature (NOAA/ASHRAE)42°F
1% cooling design temperature (NOAA/ASHRAE)108°F
Mean coincident wet bulb69°F
Design grains (75°F, 50% RH indoors)-17
Daily rangeMedium (July average 21°F)
IECC climate zone2B (Maricopa County, 2021 IECC)
Nearby stationLuke AFB (west valley) (KLUF): 37°F heating, 109°F cooling

With Manual J’s default indoor conditions of 70°F in winter and 75°F in summer, the heating load is driven by a 28°F difference and the cooling load by a 33°F difference, before sun, people and moisture are added. Design grains are negative, which means the outdoor air at the design condition is drier than the indoor target: the cooling load is almost entirely sensible.

What drives loads in Phoenix

NOAA lists Sky Harbor at 108°F cooling and 42°F heating, with negative design grains: at the design condition the outdoor air is drier than the indoor target, so the load is almost all sensible. Luke AFB in the west valley is 109°F and 37°F.

Attic ductwork is the hidden load. With ducts in a vented attic above a 108°F day, duct gain and leakage can add a large share to the room loads. Low-E glass and shading on west and south exposures make the next biggest difference.

Typical loads for Phoenix homes

Four illustrative houses, each with 8-foot ceilings and ducts in a vented attic unless noted, at the design conditions above:

HouseHeating loadCooling loadNominal sizeSq ft per ton
Older 1,500 sq ft one-story
fair insulation, double-pane windows
25,495 Btuh33,825 Btuh3 tons532
2,000 sq ft one-story, built to code
good insulation, low-E windows
21,948 Btuh29,194 Btuh2.5 tons822
2,600 sq ft two-story, built to code
good insulation, low-E windows
24,220 Btuh34,186 Btuh3 tons913
2,000 sq ft high-performance
excellent insulation and air sealing, ducts inside
15,879 Btuh22,660 Btuh2 tons1,059

The spread is the point. The older 1,500 sq ft house needs 25,495 Btuh of heat, more than the 2,000 sq ft high-performance house at 15,879 Btuh, despite being 500 sq ft smaller. No square-foot rule can see that. These are whole-house block loads from the same engine the free Manual J calculator and the app use; a room-by-room load for a real house will differ.

Common sizing mistakes in Phoenix

  • Sizing to the record high instead of the 1% design temperature. Manual J does not add safety margins.
  • Picking a condenser by its nominal tonnage. Air conditioners lose capacity as outdoor temperature rises; check the manufacturer's data at 105–115°F.
  • Ignoring the monsoon. July and August bring humid days where an oversized system short-cycles and leaves the house muggy.

Heat pumps in Phoenix

Heat pumps are the default in Phoenix, and the 42°F heating design temperature is easy. Choose by cooling performance at high ambient temperatures. The heat pump sizing guide covers reading capacity at 47°F and 17°F and setting the balance point.

Run a load for your Phoenix house

The free Manual J calculator takes a ZIP code and eight inputs and returns a whole-house heating and cooling load in the browser. The HVAC Load Calculator app goes further at the house: room-by-room loads, Manual S equipment sizes and a PDF report.

FAQ

Why not size a Phoenix AC to 115°F?

Manual J uses the 1% design temperature, 108°F at Sky Harbor, and says not to add safety factors. Above that, a right-sized system runs continuously and the house drifts a degree or two for a few hours. Sizing for the extreme leaves you oversized for the rest of the summer.

What is the Manual J design temperature for Phoenix, AZ?

NOAA’s Engineering Weather Data lists Phoenix Sky Harbor International Airport at 42°F for the 99% heating design and 108°F for the 1% cooling design, with a 69°F mean coincident wet bulb, from 1988–2017 observations. Use the station closest to the house in climate, and any value your building department requires.

What size AC do I need for a 2,000 sq ft house in Phoenix?

It depends on the house, not the floor area. In our example, a code-built 2,000 sq ft one-story with low-E windows and ducts in a vented attic comes out at about 29,194 Btuh of cooling, a 2.5-ton nominal size, or about 822 sq ft per ton. An older or leakier house needs more; run a load for the actual house.