Scope. Outdoor design conditions and illustrative block loads for homes in and around Denver, CO. The example loads are estimates for typical houses, not a design for yours. Your building department may require specific design values. Not ACCA approved or certified, and not a stamped design.
Denver design conditions
| Weather station | Buckley Space Force Base (Aurora) (KBKF) |
|---|---|
| Source | NOAA NCEI Engineering Weather Data, 1989–2018 observations |
| Elevation | 5,662 ft |
| 99% heating design temperature (NOAA/ASHRAE) | 6°F |
| 1% cooling design temperature (NOAA/ASHRAE) | 91°F |
| Mean coincident wet bulb | 59°F |
| Design grains (75°F, 50% RH indoors) | -40 |
| Daily range | High (July average 27°F) |
| IECC climate zone | 5B (Denver County, 2021 IECC) |
With Manual J’s default indoor conditions of 70°F in winter and 75°F in summer, the heating load is driven by a 64°F difference and the cooling load by a 16°F difference, before sun, people and moisture are added. Design grains are negative, which means the outdoor air at the design condition is drier than the indoor target: the cooling load is almost entirely sensible. At 5,662 feet, Manual J corrects the air density in its infiltration terms, and gas furnaces and fans deliver less than their sea-level ratings.
What drives loads in Denver
This page uses NOAA’s station at Buckley Space Force Base in Aurora, on the east side of the metro: 91°F cooling and 6°F heating, with a high daily range of about 27°F in July.
Thin air carries less heat per cubic foot. Manual J corrects the infiltration load for elevation, and gas furnaces lose capacity at altitude: the fuel gas code's general rule of 4% per 1,000 feet works out to about a fifth at Denver's elevation. Follow the furnace's own high-altitude instructions.
Typical loads for Denver homes
Four illustrative houses, each with 8-foot ceilings and ducts in the basement unless noted, at the design conditions above:
| House | Heating load | Cooling load | Nominal size | Sq ft per ton |
|---|---|---|---|---|
| Older 1,500 sq ft one-story fair insulation, double-pane windows | 47,413 Btuh | 21,175 Btuh | 2 tons | 850 |
| 2,000 sq ft one-story, built to code good insulation, low-E windows | 40,209 Btuh | 19,220 Btuh | 2 tons | 1,249 |
| 2,600 sq ft two-story, built to code good insulation, low-E windows | 44,831 Btuh | 22,086 Btuh | 2 tons | 1,413 |
| 2,000 sq ft high-performance excellent insulation and air sealing, ducts inside | 31,123 Btuh | 17,088 Btuh | 1.5 tons | 1,404 |
The spread is the point. The older 1,500 sq ft house needs 47,413 Btuh of heat, more than the 2,000 sq ft high-performance house at 31,123 Btuh, despite being 500 sq ft smaller. No square-foot rule can see that. These are whole-house block loads from the same engine the free Manual J calculator and the app use; a room-by-room load for a real house will differ.
Common sizing mistakes in Denver
- Using sea-level furnace output. A furnace that fits the load on paper can come up short at altitude.
- Sizing cooling by rules from humid cities. Denver's dry air and cool nights mean smaller cooling loads.
- Ignoring the sun. High altitude means strong solar gain through glass, even on cold days.
Heat pumps in Denver
Cold-climate heat pumps are increasingly common in Denver. At 6°F, check capacity at 5°F and confirm the manufacturer's altitude derating. The cold-climate heat pump guide walks through capacity at the design temperature, the balance point and backup heat.
Run a load for your Denver house
The free Manual J calculator takes a ZIP code and eight inputs and returns a whole-house heating and cooling load in the browser. The HVAC Load Calculator app goes further at the house: room-by-room loads, Manual S equipment sizes and a PDF report.
FAQ
Does altitude change my Denver furnace size?
Yes. Gas furnaces lose capacity in thin air, so the furnace's derated output at Denver's elevation has to cover the Manual J heat loss. Check the manufacturer's high-altitude table.
What is the Manual J design temperature for Denver, CO?
NOAA’s Engineering Weather Data lists Buckley Space Force Base (Aurora) at 6°F for the 99% heating design and 91°F for the 1% cooling design, with a 59°F mean coincident wet bulb, from 1989–2018 observations. Use the station closest to the house in climate, and any value your building department requires.
What size AC do I need for a 2,000 sq ft house in Denver?
It depends on the house, not the floor area. In our example, a code-built 2,000 sq ft one-story with low-E windows and ducts in the basement comes out at about 19,220 Btuh of cooling, a 2-ton nominal size, or about 1,249 sq ft per ton. An older or leakier house needs more; run a load for the actual house.