Scope. Outdoor design conditions and illustrative block loads for homes in and around Austin, TX. The example loads are estimates for typical houses, not a design for yours. Your building department may require specific design values. Not ACCA approved or certified, and not a stamped design.

Austin design conditions

Weather stationAustin-Bergstrom International Airport (KAUS)
SourceNOAA NCEI Engineering Weather Data, 1988–2017 observations
Elevation542 ft
99% heating design temperature (NOAA/ASHRAE)30°F
1% cooling design temperature (NOAA/ASHRAE)99°F
Mean coincident wet bulb75°F
Design grains (75°F, 50% RH indoors)25
Daily rangeMedium (July average 21°F)
IECC climate zone2A (Travis County, 2021 IECC)

With Manual J’s default indoor conditions of 70°F in winter and 75°F in summer, the heating load is driven by a 40°F difference and the cooling load by a 24°F difference, before sun, people and moisture are added. 25 design grains means a real latent load on top of the sensible load, so the equipment has to dehumidify as well as cool.

What drives loads in Austin

NOAA lists Austin-Bergstrom at 99°F cooling and 30°F heating, with 25 design grains. Summer afternoons are long and hot, and west-facing glass and attic ducts carry much of the peak.

Hill Country lots add orientation and shading variety: two identical plans on the same street can differ by half a ton depending on which way the glass faces.

Typical loads for Austin homes

Four illustrative houses, each with 8-foot ceilings and ducts in a vented attic unless noted, at the design conditions above:

HouseHeating loadCooling loadNominal sizeSq ft per ton
Older 1,500 sq ft one-story
fair insulation, double-pane windows
34,802 Btuh33,747 Btuh3 tons533
2,000 sq ft one-story, built to code
good insulation, low-E windows
29,692 Btuh29,707 Btuh2.5 tons808
2,600 sq ft two-story, built to code
good insulation, low-E windows
32,964 Btuh34,514 Btuh3 tons904
2,000 sq ft high-performance
excellent insulation and air sealing, ducts inside
21,213 Btuh23,437 Btuh2 tons1,024

The spread is the point. The older 1,500 sq ft house needs 34,802 Btuh of heat, more than the 2,000 sq ft high-performance house at 21,213 Btuh, despite being 500 sq ft smaller. No square-foot rule can see that. These are whole-house block loads from the same engine the free Manual J calculator and the app use; a room-by-room load for a real house will differ.

Common sizing mistakes in Austin

  • Sizing to the February 2021 freeze. Manual J uses the 99% heating design temperature, not the record. Cover rare extremes with backup heat, not a bigger system.
  • Ignoring the attic. Unvented, sprayed-foam attics change the duct load completely; enter what the house actually has.
  • Leaving orientation at a default on a house with walls of glass.

Heat pumps in Austin

Heat pumps are common in Austin, and at a 30°F design temperature a standard heat pump covers most of the heating season. Pair it with right-sized strip heat for freeze events. The heat pump sizing guide covers reading capacity at 47°F and 17°F and setting the balance point.

Run a load for your Austin house

The free Manual J calculator takes a ZIP code and eight inputs and returns a whole-house heating and cooling load in the browser. The HVAC Load Calculator app goes further at the house: room-by-room loads, Manual S equipment sizes and a PDF report.

FAQ

Should I size my Austin heat pump for a hard freeze?

No. Size to the 99% heating design temperature, 30°F at Austin-Bergstrom, and cover rarer cold with backup heat. A system sized for a record freeze would be badly oversized for cooling all summer.

What is the Manual J design temperature for Austin, TX?

NOAA’s Engineering Weather Data lists Austin-Bergstrom International Airport at 30°F for the 99% heating design and 99°F for the 1% cooling design, with a 75°F mean coincident wet bulb, from 1988–2017 observations. Use the station closest to the house in climate, and any value your building department requires.

What size AC do I need for a 2,000 sq ft house in Austin?

It depends on the house, not the floor area. In our example, a code-built 2,000 sq ft one-story with low-E windows and ducts in a vented attic comes out at about 29,707 Btuh of cooling, a 2.5-ton nominal size, or about 808 sq ft per ton. An older or leakier house needs more; run a load for the actual house.