Scope. Outdoor design conditions and illustrative block loads for homes in and around Austin, TX. The example loads are estimates for typical houses, not a design for yours. Your building department may require specific design values. Not ACCA approved or certified, and not a stamped design.
Austin design conditions
| Weather station | Austin-Bergstrom International Airport (KAUS) |
|---|---|
| Source | NOAA NCEI Engineering Weather Data, 1988–2017 observations |
| Elevation | 542 ft |
| 99% heating design temperature (NOAA/ASHRAE) | 30°F |
| 1% cooling design temperature (NOAA/ASHRAE) | 99°F |
| Mean coincident wet bulb | 75°F |
| Design grains (75°F, 50% RH indoors) | 25 |
| Daily range | Medium (July average 21°F) |
| IECC climate zone | 2A (Travis County, 2021 IECC) |
With Manual J’s default indoor conditions of 70°F in winter and 75°F in summer, the heating load is driven by a 40°F difference and the cooling load by a 24°F difference, before sun, people and moisture are added. 25 design grains means a real latent load on top of the sensible load, so the equipment has to dehumidify as well as cool.
What drives loads in Austin
NOAA lists Austin-Bergstrom at 99°F cooling and 30°F heating, with 25 design grains. Summer afternoons are long and hot, and west-facing glass and attic ducts carry much of the peak.
Hill Country lots add orientation and shading variety: two identical plans on the same street can differ by half a ton depending on which way the glass faces.
Typical loads for Austin homes
Four illustrative houses, each with 8-foot ceilings and ducts in a vented attic unless noted, at the design conditions above:
| House | Heating load | Cooling load | Nominal size | Sq ft per ton |
|---|---|---|---|---|
| Older 1,500 sq ft one-story fair insulation, double-pane windows | 34,802 Btuh | 33,747 Btuh | 3 tons | 533 |
| 2,000 sq ft one-story, built to code good insulation, low-E windows | 29,692 Btuh | 29,707 Btuh | 2.5 tons | 808 |
| 2,600 sq ft two-story, built to code good insulation, low-E windows | 32,964 Btuh | 34,514 Btuh | 3 tons | 904 |
| 2,000 sq ft high-performance excellent insulation and air sealing, ducts inside | 21,213 Btuh | 23,437 Btuh | 2 tons | 1,024 |
The spread is the point. The older 1,500 sq ft house needs 34,802 Btuh of heat, more than the 2,000 sq ft high-performance house at 21,213 Btuh, despite being 500 sq ft smaller. No square-foot rule can see that. These are whole-house block loads from the same engine the free Manual J calculator and the app use; a room-by-room load for a real house will differ.
Common sizing mistakes in Austin
- Sizing to the February 2021 freeze. Manual J uses the 99% heating design temperature, not the record. Cover rare extremes with backup heat, not a bigger system.
- Ignoring the attic. Unvented, sprayed-foam attics change the duct load completely; enter what the house actually has.
- Leaving orientation at a default on a house with walls of glass.
Heat pumps in Austin
Heat pumps are common in Austin, and at a 30°F design temperature a standard heat pump covers most of the heating season. Pair it with right-sized strip heat for freeze events. The heat pump sizing guide covers reading capacity at 47°F and 17°F and setting the balance point.
Run a load for your Austin house
The free Manual J calculator takes a ZIP code and eight inputs and returns a whole-house heating and cooling load in the browser. The HVAC Load Calculator app goes further at the house: room-by-room loads, Manual S equipment sizes and a PDF report.
FAQ
Should I size my Austin heat pump for a hard freeze?
No. Size to the 99% heating design temperature, 30°F at Austin-Bergstrom, and cover rarer cold with backup heat. A system sized for a record freeze would be badly oversized for cooling all summer.
What is the Manual J design temperature for Austin, TX?
NOAA’s Engineering Weather Data lists Austin-Bergstrom International Airport at 30°F for the 99% heating design and 99°F for the 1% cooling design, with a 75°F mean coincident wet bulb, from 1988–2017 observations. Use the station closest to the house in climate, and any value your building department requires.
What size AC do I need for a 2,000 sq ft house in Austin?
It depends on the house, not the floor area. In our example, a code-built 2,000 sq ft one-story with low-E windows and ducts in a vented attic comes out at about 29,707 Btuh of cooling, a 2.5-ton nominal size, or about 808 sq ft per ton. An older or leakier house needs more; run a load for the actual house.