Scope. Outdoor design conditions and illustrative block loads for homes in and around Chicago, IL. The example loads are estimates for typical houses, not a design for yours. Your building department may require specific design values. Not ACCA approved or certified, and not a stamped design.
Chicago design conditions
| Weather station | O'Hare International Airport (KORD) |
|---|---|
| Source | NOAA NCEI Engineering Weather Data, 1988–2017 observations |
| Elevation | 668 ft |
| 99% heating design temperature (NOAA/ASHRAE) | 3°F |
| 1% cooling design temperature (NOAA/ASHRAE) | 89°F |
| Mean coincident wet bulb | 73°F |
| Design grains (75°F, 50% RH indoors) | 33 |
| Daily range | Medium (July average 18°F) |
| IECC climate zone | 5A (Cook County, 2021 IECC) |
| Nearby station | Midway Airport (KMDW): 5°F heating, 90°F cooling |
With Manual J’s default indoor conditions of 70°F in winter and 75°F in summer, the heating load is driven by a 67°F difference and the cooling load by a 14°F difference, before sun, people and moisture are added. 33 design grains means a real latent load on top of the sensible load, so the equipment has to dehumidify as well as cool.
What drives loads in Chicago
NOAA lists O'Hare at 89°F cooling and 3°F heating, with 33 design grains. Midway is 90°F and 5°F; the lake moderates temperatures near the shore.
Basements with the furnace and ducts below the main floor are standard. Brick bungalows and two-flats with little wall insulation have high heat losses per square foot.
Typical loads for Chicago homes
Four illustrative houses, each with 8-foot ceilings and ducts in the basement unless noted, at the design conditions above:
| House | Heating load | Cooling load | Nominal size | Sq ft per ton |
|---|---|---|---|---|
| Older 1,500 sq ft one-story fair insulation, double-pane windows | 53,018 Btuh | 25,669 Btuh | 2.5 tons | 701 |
| 2,000 sq ft one-story, built to code good insulation, low-E windows | 45,003 Btuh | 23,263 Btuh | 2 tons | 1,032 |
| 2,600 sq ft two-story, built to code good insulation, low-E windows | 49,966 Btuh | 26,713 Btuh | 2.5 tons | 1,168 |
| 2,000 sq ft high-performance excellent insulation and air sealing, ducts inside | 34,850 Btuh | 20,653 Btuh | 2 tons | 1,162 |
The spread is the point. The older 1,500 sq ft house needs 53,018 Btuh of heat, more than the 2,000 sq ft high-performance house at 34,850 Btuh, despite being 500 sq ft smaller. No square-foot rule can see that. These are whole-house block loads from the same engine the free Manual J calculator and the app use; a room-by-room load for a real house will differ.
Common sizing mistakes in Chicago
- Sizing the furnace to the old one. Many Chicago furnaces were oversized decades ago.
- Forgetting the input vs output difference when moving to a high-efficiency furnace.
- Treating a finished basement as unconditioned.
Heat pumps in Chicago
At 3°F, only cold-climate heat pumps keep meaningful capacity; many Chicago installs pair a heat pump with a gas furnace. Check capacity at 5°F and set the balance point from the Manual J heat loss. The cold-climate heat pump guide walks through capacity at the design temperature, the balance point and backup heat.
Run a load for your Chicago house
The free Manual J calculator takes a ZIP code and eight inputs and returns a whole-house heating and cooling load in the browser. The HVAC Load Calculator app goes further at the house: room-by-room loads, Manual S equipment sizes and a PDF report.
FAQ
What size furnace does a Chicago house need?
Whatever the Manual J heat loss at 3°F says, landed in the Manual S window. A code-built 2,000 sq ft house often needs much less furnace output than the one it is replacing, especially if that one dates from before the house got new windows or insulation.
What is the Manual J design temperature for Chicago, IL?
NOAA’s Engineering Weather Data lists O'Hare International Airport at 3°F for the 99% heating design and 89°F for the 1% cooling design, with a 73°F mean coincident wet bulb, from 1988–2017 observations. Use the station closest to the house in climate, and any value your building department requires.
What size AC do I need for a 2,000 sq ft house in Chicago?
It depends on the house, not the floor area. In our example, a code-built 2,000 sq ft one-story with low-E windows and ducts in the basement comes out at about 23,263 Btuh of cooling, a 2-ton nominal size, or about 1,032 sq ft per ton. An older or leakier house needs more; run a load for the actual house.