Scope. Outdoor design conditions and illustrative block loads for homes in and around Portland, OR. The example loads are estimates for typical houses, not a design for yours. Your building department may require specific design values. Not ACCA approved or certified, and not a stamped design.
Portland design conditions
| Weather station | Portland International Airport (KPDX) |
|---|---|
| Source | NOAA NCEI Engineering Weather Data, 1988–2017 observations |
| Elevation | 30 ft |
| 99% heating design temperature (NOAA/ASHRAE) | 29°F |
| 1% cooling design temperature (NOAA/ASHRAE) | 88°F |
| Mean coincident wet bulb | 67°F |
| Design grains (75°F, 50% RH indoors) | -1 |
| Daily range | Medium (July average 22°F) |
| IECC climate zone | 4C (Multnomah County, 2021 IECC) |
With Manual J’s default indoor conditions of 70°F in winter and 75°F in summer, the heating load is driven by a 41°F difference and the cooling load by a 13°F difference, before sun, people and moisture are added. Design grains are negative, which means the outdoor air at the design condition is drier than the indoor target: the cooling load is almost entirely sensible.
What drives loads in Portland
NOAA lists Portland International at 88°F cooling and 29°F heating, with negative design grains and a medium daily range.
Older homes on crawlspaces and basements with ducts added later are common. East-side neighborhoods take more of the Gorge wind in winter, which raises infiltration on windy cold nights.
Typical loads for Portland homes
Four illustrative houses, each with 8-foot ceilings and ducts in a vented crawlspace unless noted, at the design conditions above:
| House | Heating load | Cooling load | Nominal size | Sq ft per ton |
|---|---|---|---|---|
| Older 1,500 sq ft one-story fair insulation, double-pane windows | 34,667 Btuh | 23,409 Btuh | 2 tons | 769 |
| 2,000 sq ft one-story, built to code good insulation, low-E windows | 29,450 Btuh | 21,332 Btuh | 2 tons | 1,125 |
| 2,600 sq ft two-story, built to code good insulation, low-E windows | 32,782 Btuh | 24,450 Btuh | 2.5 tons | 1,276 |
| 2,000 sq ft high-performance excellent insulation and air sealing, ducts inside | 21,901 Btuh | 18,155 Btuh | 2 tons | 1,322 |
The spread is the point. The older 1,500 sq ft house needs 34,667 Btuh of heat, more than the 2,000 sq ft high-performance house at 21,901 Btuh, despite being 500 sq ft smaller. No square-foot rule can see that. These are whole-house block loads from the same engine the free Manual J calculator and the app use; a room-by-room load for a real house will differ.
Common sizing mistakes in Portland
- Sizing to the 2021 heat dome. Rare extremes are not design conditions.
- Ignoring infiltration in older homes, where wind-driven leakage is a big part of the heat loss.
- Undersizing the backup heat on a standard heat pump in an exposed house.
Heat pumps in Portland
Heat pumps suit Portland well. At 29°F they carry most of the heating season; check the 17°F capacity and size backup for the coldest, windiest nights. The heat pump sizing guide covers reading capacity at 47°F and 17°F and setting the balance point.
Run a load for your Portland house
The free Manual J calculator takes a ZIP code and eight inputs and returns a whole-house heating and cooling load in the browser. The HVAC Load Calculator app goes further at the house: room-by-room loads, Manual S equipment sizes and a PDF report.
FAQ
Is Portland's design temperature the same as Seattle's?
Close for heating: 29°F at Portland International versus 30°F at Sea-Tac. Portland's cooling design temperature is 88°F versus 82°F, so Portland homes usually have a bigger cooling load.
What is the Manual J design temperature for Portland, OR?
NOAA’s Engineering Weather Data lists Portland International Airport at 29°F for the 99% heating design and 88°F for the 1% cooling design, with a 67°F mean coincident wet bulb, from 1988–2017 observations. Use the station closest to the house in climate, and any value your building department requires.
What size AC do I need for a 2,000 sq ft house in Portland?
It depends on the house, not the floor area. In our example, a code-built 2,000 sq ft one-story with low-E windows and ducts in a vented crawlspace comes out at about 21,332 Btuh of cooling, a 2-ton nominal size, or about 1,125 sq ft per ton. An older or leakier house needs more; run a load for the actual house.