Scope. Outdoor design conditions and illustrative block loads for homes in and around Portland, OR. The example loads are estimates for typical houses, not a design for yours. Your building department may require specific design values. Not ACCA approved or certified, and not a stamped design.

Portland design conditions

Weather stationPortland International Airport (KPDX)
SourceNOAA NCEI Engineering Weather Data, 1988–2017 observations
Elevation30 ft
99% heating design temperature (NOAA/ASHRAE)29°F
1% cooling design temperature (NOAA/ASHRAE)88°F
Mean coincident wet bulb67°F
Design grains (75°F, 50% RH indoors)-1
Daily rangeMedium (July average 22°F)
IECC climate zone4C (Multnomah County, 2021 IECC)

With Manual J’s default indoor conditions of 70°F in winter and 75°F in summer, the heating load is driven by a 41°F difference and the cooling load by a 13°F difference, before sun, people and moisture are added. Design grains are negative, which means the outdoor air at the design condition is drier than the indoor target: the cooling load is almost entirely sensible.

What drives loads in Portland

NOAA lists Portland International at 88°F cooling and 29°F heating, with negative design grains and a medium daily range.

Older homes on crawlspaces and basements with ducts added later are common. East-side neighborhoods take more of the Gorge wind in winter, which raises infiltration on windy cold nights.

Typical loads for Portland homes

Four illustrative houses, each with 8-foot ceilings and ducts in a vented crawlspace unless noted, at the design conditions above:

HouseHeating loadCooling loadNominal sizeSq ft per ton
Older 1,500 sq ft one-story
fair insulation, double-pane windows
34,667 Btuh23,409 Btuh2 tons769
2,000 sq ft one-story, built to code
good insulation, low-E windows
29,450 Btuh21,332 Btuh2 tons1,125
2,600 sq ft two-story, built to code
good insulation, low-E windows
32,782 Btuh24,450 Btuh2.5 tons1,276
2,000 sq ft high-performance
excellent insulation and air sealing, ducts inside
21,901 Btuh18,155 Btuh2 tons1,322

The spread is the point. The older 1,500 sq ft house needs 34,667 Btuh of heat, more than the 2,000 sq ft high-performance house at 21,901 Btuh, despite being 500 sq ft smaller. No square-foot rule can see that. These are whole-house block loads from the same engine the free Manual J calculator and the app use; a room-by-room load for a real house will differ.

Common sizing mistakes in Portland

  • Sizing to the 2021 heat dome. Rare extremes are not design conditions.
  • Ignoring infiltration in older homes, where wind-driven leakage is a big part of the heat loss.
  • Undersizing the backup heat on a standard heat pump in an exposed house.

Heat pumps in Portland

Heat pumps suit Portland well. At 29°F they carry most of the heating season; check the 17°F capacity and size backup for the coldest, windiest nights. The heat pump sizing guide covers reading capacity at 47°F and 17°F and setting the balance point.

Run a load for your Portland house

The free Manual J calculator takes a ZIP code and eight inputs and returns a whole-house heating and cooling load in the browser. The HVAC Load Calculator app goes further at the house: room-by-room loads, Manual S equipment sizes and a PDF report.

FAQ

Is Portland's design temperature the same as Seattle's?

Close for heating: 29°F at Portland International versus 30°F at Sea-Tac. Portland's cooling design temperature is 88°F versus 82°F, so Portland homes usually have a bigger cooling load.

What is the Manual J design temperature for Portland, OR?

NOAA’s Engineering Weather Data lists Portland International Airport at 29°F for the 99% heating design and 88°F for the 1% cooling design, with a 67°F mean coincident wet bulb, from 1988–2017 observations. Use the station closest to the house in climate, and any value your building department requires.

What size AC do I need for a 2,000 sq ft house in Portland?

It depends on the house, not the floor area. In our example, a code-built 2,000 sq ft one-story with low-E windows and ducts in a vented crawlspace comes out at about 21,332 Btuh of cooling, a 2-ton nominal size, or about 1,125 sq ft per ton. An older or leakier house needs more; run a load for the actual house.