Core · De minimis
Which release counts as de minimis and is NOT a violation of the venting prohibition?
- Purging part of the charge to clear a restriction
- Venting a nearly empty system to save recovery time
- Using the system refrigerant as a leak-test gas and releasing it
- Small hose losses at disconnect after proper recovery
Answer
D. De minimis releases are the small, unavoidable losses that occur during a good-faith effort to recover refrigerant with certified equipment and required practices. Deliberate releases to save time or test for leaks are violations.
-
Core · Sales restriction
Who may buy refrigerant such as R-22 or R-410A for servicing stationary equipment?
- Anyone, as long as each cylinder holds less than 30 lb
- Anyone who holds a state mechanical or HVAC contractor license
- A certified technician or an employer of one, with proof
- Only reclaimers and equipment manufacturers
Answer
C. The sales restriction limits refrigerant sales to certified technicians, employers of certified technicians who provide proof, and a few other listed buyers such as manufacturers and resellers.
-
Core · Blends
Fractionation in a zeotropic refrigerant blend means:
- The blend separates into oil and refrigerant layers in storage
- The blend turns into an azeotrope after any leak
- Its components leak or boil off at different rates
- The pressure falls below the saturation curve
Answer
C. The components of a zeotropic blend have different boiling points, so a vapor leak or vapor charging can remove more of one component than another and shift the blend's composition.
-
Type I · Small appliance definition
Under Section 608, a "small appliance" is one that is:
- Any sealed or field-built system that holds less than 15 lb of refrigerant
- Factory-built, factory-charged, and hermetically sealed with 5 lb or less
- Any appliance that plugs into a standard 120 V household outlet
- Installed and charged in the field with 5 lb or less of refrigerant
Answer
B. The definition has two parts: the unit must be built, charged, and hermetically sealed at the factory, and it must hold 5 lb or less. A field-charged system does not qualify even if its charge is small.
-
Type I · Recovery requirements
Using recovery equipment made on or after November 15, 1993, how much refrigerant must be recovered from a small appliance whose compressor works?
- 80 percent
- 90 percent
- 95 percent
- 99 percent
Answer
B. With newer equipment and a functioning compressor, 90 percent of the charge must be recovered. The alternative is to evacuate the appliance to 4 inches of mercury vacuum.
-
Type I · Recovery equipment
System-dependent (passive) recovery equipment relies on:
- A separate compressor built into the recovery machine
- A nitrogen push through the refrigerant circuit
- The appliance's compressor or its internal pressure
- Gravity alone, with the appliance turned upside down
Answer
C. By definition, system-dependent equipment needs components contained in the appliance, such as its compressor, or the refrigerant's own pressure, to remove the refrigerant.
-
Type II · Pressure categories
Under the current Section 608 definitions, a high-pressure appliance uses a refrigerant whose liquid saturation pressure at 104°F is:
- Below 45 psia
- Between 45 and 170 psia
- Between 170 and 355 psia
- Above 355 psia
Answer
C. EPA sorts appliances by the refrigerant’s saturation pressure at 104°F. 170–355 psia is high pressure (R-22, R-407C, R-410A); 45–170 psia is medium pressure and below 45 psia is low pressure. Older guides use the pre-2017 boiling-point definitions instead.
-
Type II · Evacuation levels
Using a recovery machine built after November 15, 1993, what level must an R-22 system with a 150-pound full charge reach before it is opened for a major repair?
- 10 inches of Hg vacuum
- 4 inches of Hg vacuum
- 15 inches of Hg vacuum
- 0 inches of Hg vacuum (0 psig)
Answer
D. For a high-pressure appliance or isolated component with a full charge under 200 lb, Table 1 requires 0 in. Hg vacuum whether the recovery machine is old or new. Deeper levels apply only at 200 lb and up. The current table puts R-410A and R-404A in this same row; older guides with a separate HCFC-22 row may show 10 in. Hg for them.
-
Type II · Leak repair thresholds
As of 2026, an R-22 comfort-cooling chiller with a 200-pound full charge must have leaks repaired once its leak rate exceeds:
Answer
D. For appliances with 50 lb or more of ozone-depleting refrigerant, comfort cooling (and “all other”) appliances have a 10% leak-rate trigger. 20% is commercial refrigeration and 30% is industrial process refrigeration.
-
Type III · Pressure-temperature
An idle R-123 chiller sits in a 70°F equipment room. What will a gauge on the refrigerant side show?
- About 70 psig
- About 15 psig, at the rupture-disc setting
- Exactly 0 psig
- A vacuum, below 0 psig
Answer
D. R-123 boils at about 82°F at atmospheric pressure, so at 70°F its saturation pressure is below atmospheric and the gauge reads a vacuum. This is why idle low-pressure chillers can still draw air in through leaks.
-
Type III · Leak signs
The purge unit on a chiller now runs much more often than its normal logged run time. This most likely means:
- The chiller is lightly loaded
- The refrigerant charge is too high
- Air is leaking into the system
- The chilled-water temperature is set too high
Answer
C. Excessive purging is the classic sign of a leak into a low-pressure system. Tracking purge run time or pump-out counts is an early leak indicator.
-
Type III · Leak testing
Why must the refrigerant side of a low-pressure chiller be brought above atmospheric pressure before searching for leaks?
- Electronic leak detectors do not work in indoor machinery rooms
- Below atmospheric pressure, leaks pull air in, so no refrigerant escapes to detect
- It is needed to reset the purge counter
- The rupture disc only seals properly when the shell is under positive pressure
Answer
B. While the shell is in a vacuum, leaks flow inward and a detector has nothing to sense. A slight positive pressure, kept within the safe limit, pushes refrigerant out at the leak.
240+ more EPA 608 questions, section mocks scored 18 of 25, a 100-question Universal mock, and A2L safety prep — free, offline, no account.