EPA 608 practice test: 12 free questions with answers

Three original exam-style questions from each section of the EPA Section 608 technician exam: Core, Type I, Type II and Type III. Answer, then expand the explanation. The A2L & EPA 608 Test Prep app has 250+ EPA 608 questions, 25-question section mocks and a 100-question Universal mock — free and offline.

Independent study material. Not affiliated with, endorsed by, or approved by the U.S. EPA, ESCO Institute, Mainstream Engineering, or any certifying organization.

  1. Core · De minimis

    Which release counts as de minimis and is NOT a violation of the venting prohibition?

    • Purging part of the charge to clear a restriction
    • Venting a nearly empty system to save recovery time
    • Using the system refrigerant as a leak-test gas and releasing it
    • Small hose losses at disconnect after proper recovery
    Answer

    D. De minimis releases are the small, unavoidable losses that occur during a good-faith effort to recover refrigerant with certified equipment and required practices. Deliberate releases to save time or test for leaks are violations.

  2. Core · Sales restriction

    Who may buy refrigerant such as R-22 or R-410A for servicing stationary equipment?

    • Anyone, as long as each cylinder holds less than 30 lb
    • Anyone who holds a state mechanical or HVAC contractor license
    • A certified technician or an employer of one, with proof
    • Only reclaimers and equipment manufacturers
    Answer

    C. The sales restriction limits refrigerant sales to certified technicians, employers of certified technicians who provide proof, and a few other listed buyers such as manufacturers and resellers.

  3. Core · Blends

    Fractionation in a zeotropic refrigerant blend means:

    • The blend separates into oil and refrigerant layers in storage
    • The blend turns into an azeotrope after any leak
    • Its components leak or boil off at different rates
    • The pressure falls below the saturation curve
    Answer

    C. The components of a zeotropic blend have different boiling points, so a vapor leak or vapor charging can remove more of one component than another and shift the blend's composition.

  4. Type I · Small appliance definition

    Under Section 608, a "small appliance" is one that is:

    • Any sealed or field-built system that holds less than 15 lb of refrigerant
    • Factory-built, factory-charged, and hermetically sealed with 5 lb or less
    • Any appliance that plugs into a standard 120 V household outlet
    • Installed and charged in the field with 5 lb or less of refrigerant
    Answer

    B. The definition has two parts: the unit must be built, charged, and hermetically sealed at the factory, and it must hold 5 lb or less. A field-charged system does not qualify even if its charge is small.

  5. Type I · Recovery requirements

    Using recovery equipment made on or after November 15, 1993, how much refrigerant must be recovered from a small appliance whose compressor works?

    • 80 percent
    • 90 percent
    • 95 percent
    • 99 percent
    Answer

    B. With newer equipment and a functioning compressor, 90 percent of the charge must be recovered. The alternative is to evacuate the appliance to 4 inches of mercury vacuum.

  6. Type I · Recovery equipment

    System-dependent (passive) recovery equipment relies on:

    • A separate compressor built into the recovery machine
    • A nitrogen push through the refrigerant circuit
    • The appliance's compressor or its internal pressure
    • Gravity alone, with the appliance turned upside down
    Answer

    C. By definition, system-dependent equipment needs components contained in the appliance, such as its compressor, or the refrigerant's own pressure, to remove the refrigerant.

  7. Type II · Pressure categories

    Under the current Section 608 definitions, a high-pressure appliance uses a refrigerant whose liquid saturation pressure at 104°F is:

    • Below 45 psia
    • Between 45 and 170 psia
    • Between 170 and 355 psia
    • Above 355 psia
    Answer

    C. EPA sorts appliances by the refrigerant’s saturation pressure at 104°F. 170–355 psia is high pressure (R-22, R-407C, R-410A); 45–170 psia is medium pressure and below 45 psia is low pressure. Older guides use the pre-2017 boiling-point definitions instead.

  8. Type II · Evacuation levels

    Using a recovery machine built after November 15, 1993, what level must an R-22 system with a 150-pound full charge reach before it is opened for a major repair?

    • 10 inches of Hg vacuum
    • 4 inches of Hg vacuum
    • 15 inches of Hg vacuum
    • 0 inches of Hg vacuum (0 psig)
    Answer

    D. For a high-pressure appliance or isolated component with a full charge under 200 lb, Table 1 requires 0 in. Hg vacuum whether the recovery machine is old or new. Deeper levels apply only at 200 lb and up. The current table puts R-410A and R-404A in this same row; older guides with a separate HCFC-22 row may show 10 in. Hg for them.

  9. Type II · Leak repair thresholds

    As of 2026, an R-22 comfort-cooling chiller with a 200-pound full charge must have leaks repaired once its leak rate exceeds:

    • 5%
    • 20%
    • 30%
    • 10%
    Answer

    D. For appliances with 50 lb or more of ozone-depleting refrigerant, comfort cooling (and “all other”) appliances have a 10% leak-rate trigger. 20% is commercial refrigeration and 30% is industrial process refrigeration.

  10. Type III · Pressure-temperature

    An idle R-123 chiller sits in a 70°F equipment room. What will a gauge on the refrigerant side show?

    • About 70 psig
    • About 15 psig, at the rupture-disc setting
    • Exactly 0 psig
    • A vacuum, below 0 psig
    Answer

    D. R-123 boils at about 82°F at atmospheric pressure, so at 70°F its saturation pressure is below atmospheric and the gauge reads a vacuum. This is why idle low-pressure chillers can still draw air in through leaks.

  11. Type III · Leak signs

    The purge unit on a chiller now runs much more often than its normal logged run time. This most likely means:

    • The chiller is lightly loaded
    • The refrigerant charge is too high
    • Air is leaking into the system
    • The chilled-water temperature is set too high
    Answer

    C. Excessive purging is the classic sign of a leak into a low-pressure system. Tracking purge run time or pump-out counts is an early leak indicator.

  12. Type III · Leak testing

    Why must the refrigerant side of a low-pressure chiller be brought above atmospheric pressure before searching for leaks?

    • Electronic leak detectors do not work in indoor machinery rooms
    • Below atmospheric pressure, leaks pull air in, so no refrigerant escapes to detect
    • It is needed to reset the purge counter
    • The rupture disc only seals properly when the shell is under positive pressure
    Answer

    B. While the shell is in a vacuum, leaks flow inward and a detector has nothing to sense. A slight positive pressure, kept within the safe limit, pushes refrigerant out at the leak.

240+ more EPA 608 questions, section mocks scored 18 of 25, a 100-question Universal mock, and A2L safety prep — free, offline, no account.

About the exam

How EPA 608 certification works

Who needs EPA 608 certification?

Anyone who maintains, services, repairs or disposes of equipment in a way that could release refrigerant into the atmosphere, under 40 CFR 82.161. Certification is also needed to buy most refrigerants for stationary equipment: the sales restriction limits sales to certified technicians and employers of certified technicians.

How is the EPA 608 exam structured?

Four sections: Core, Type I (small appliances), Type II (high-pressure and very-high-pressure appliances) and Type III (low-pressure appliances). Each section is commonly 25 questions, and 18 correct (72%) is the commonly published passing score for each. You pass Core plus at least one Type; passing all four is Universal certification. Some providers offer Type I as an open-book test with its own passing score, so check your provider.

Does EPA 608 certification expire?

No. Section 608 technician certification does not expire. Keep your card or certificate, because refrigerant sellers and employers can ask to see it.

Is this the real EPA 608 test?

No. These are original practice questions written for the A2L & EPA 608 Test Prep app and checked against 40 CFR Part 82 Subpart F and Part 84 as of 2026. They are not copied from any exam or question bank. Certification comes only from a proctored test given by an EPA-approved certifying organization.

Found a question you think is wrong?

Corrections are welcome at mike@hvacloadcalculator.online. The bank is original material reviewed against the regulations it cites.